External Battery Connector (Select Models Only)

Use to connect additional Tripp Lite battery packs for additional runtime. Refer to the label next to the connector for the appro- priate Tripp Lite battery pack to connect. Refer to instructions available with the battery pack for complete connection informa- tion and safety warnings.

Battery Replacement Door

Under normal conditions, the original battery in your UPS will last several years. Battery replacement should be performed only by qualified service personnel. Refer to “Battery Warnings” in the Safety section on page 2.

Storage & Service

Storage

Turn your UPS OFF: first engage the ON/Standby Switch and release it to place your UPS in the “Standby” mode, then disconnect the UPS power cord from the wall outlet. If you plan on storing your UPS for an extended period of time, recharge the UPS batteries once every three months. Follow steps #1 and #3 in the Quick Installation section and allow the UPS to charge from 4 to 6 hours. If you leave your UPS batteries discharged for an extended period of time, they will suffer permanent loss of capacity.

Service

If returning your UPS for service, contact your local Tripp Lite dealer or distributor. They will refer you to a service center. Please carefully pack the UPS using the ORIGINAL PACKING MATERIAL that came with the unit. Enclose a letter describing the symptoms of the problem. If the UPS is within the 2 year warranty period, enclose a copy of your sales receipt.

Specifications

 

Smart INT 450

Smart INT 700

Smart INT 1000

Output Capacity (VA/Watts):

450/280

700/425

1000/680

Battery Runtime (Half Load/

 

 

 

Full Load) Minutes:

19/5

20/6

23/8

Battery Recharge Time:

2-4 hrs.

2-4 hrs.

2-4 hrs.

Approvals:

UL, CE

UL, CE

UL, CE

 

Smart INT 1400

Smart INT 1400 XL

 

Output Capacity (VA/Watts):

1400/940

1400/940

 

Battery Runtime (Half Load/

 

 

 

Full Load) Minutes:

25/10

25+/10+*

 

Battery Recharge Time:

2-4 hrs.

2-4 hrs.

 

Approvals:

UL, CE

UL, CE

 

* Battery Runtime for this model can be increased with the addition of optional external battery packs.

Input Voltage (230V); Input Frequency (50/60 Hz, Auto-Selecting); On-Line Input Voltage Range (151-274 volts); Voltage-Regulated Output Voltage Range (230V +6%/-15%); On-Battery Output Voltage Range (230V ± 5%); Output Waveform Line Mode (filtered sinewave); Output Waveform Battery Mode (PWM sine wave); AC Surge Suppression (exceeds IEEE 587 Cat. A & B standards); AC Noise Attenuation (>40 dB); AC TVSS Protection Modes (H to N, H to G, N to G).

The policy of Tripp Lite is one of continuous improvement. Specifications are subject to change.

6

Page 6
Image 6
Tripp Lite 450-1400VA specifications Storage & Service, Specifications