Appendix B
H-100 DIGITAL OUTPUT FUNCTIONS
| Number | Default Function Name | Function Description |
|
| 1 | COMMON ALARM | An alarm is active |
|
| 2 | COMMON WARNING | A warning is active |
|
| 3 | GEN RUNNING | Generator is running |
|
| 4 | ALARMS ENABLED | All alarm hold off delays have expired, so all alarms are enabled |
|
| 5 | READY FOR LOAD | Generator is warmed up and ready to accept power loading |
|
| 6 | GEN READY TO RUN | Generator is ready to start |
|
| 7 | GEN | Generator stopped due to a shutdown alarm |
|
| 8 | GEN STOPPED | Generator is stopped |
|
| 9 | GEN IN MANUAL | Generator in MANUAL mode ( key switch in MANUAL or ILC overriden) |
|
| 10 | GEN IN AUTO | Generator in AUTO mode ( key switch in AUTO or ILC overriden ) |
|
| 11 | GEN IN OFF | Generator in OFF mode ( key switch in OFF or ILC overriden ) |
|
| 12 | OVERCRANK ALARM | Generator has unsuccessfully tried to start the designated number of times |
|
| 13 | OIL INHIBIT ALRM | Oil pressure too high for a stopped engine |
|
| 14 | ANNUNC SPR LIGHT | ILC controlled: this function operates the spare remote annunciator light |
|
| 15 | OIL TEMP HI ALRM | Oil Temperature has gone above maximum alarm limit |
|
| 16 | OIL TEMP LO ALRM | Oil Temperature has gone below minimum alarm limit |
|
| 17 | OIL TEMP HI WARN | Oil Temperature has gone above maximum warning limit |
|
| 18 | OIL TEMP LO WARN | Oil Temperature has gone below maximum warning limit |
|
| 19 | OIL TEMP FAULT | Oil Temperature sensor exceeds nominal limits for valid sensor reading |
|
| 20 | COOL TMP HI ALRM | Coolant Temperature has gone above maximum alarm limit |
|
| 21 | COOL TMP LO ALRM | Coolant Temperature has gone below minimum alarm limit |
|
| 22 | COOL TMP HI WARN | Coolant Temperature has gone above maximum warning limit |
|
| 23 | COOL TMP LO WARN | Coolant Temperature has gone below maximum warning limit |
|
| 24 | COOL TMP FAULT | Coolant Temperature sensor exceeds nominal limits for valid sensor reading |
|
| 25 | OIL PRES HI ALRM | Oil Pressure has gone above maximum alarm limit |
|
| 26 | OIL PRES LO ALRM | Oil Pressure has gone below minimum alarm limit |
|
| 27 | OIL PRES HI WARN | Oil Pressure has gone above maximum warning limit |
|
| 28 | OIL PRES LO WARN | Oil Pressure has gone below maximum warning limit |
|
| 29 | OIL PRES FAULT | Oil Pressure sensor exceeds nominal limits for valid sensor reading |
|
| 30 | COOL LVL HI ALRM | Coolant Level has gone above maximum alarm limit |
|
| 31 | COOL LVL LO ALRM | Coolant Level has gone below minimum alarm limit |
|
| 32 | COOL LVL HI WARN | Coolant Level has gone above maximum warning limit |
|
| 33 | COOL LVL LO WARN | Coolant Level has gone below maximum warning limit |
|
| 34 | COOL LVL FAULT | Coolant Level sensor exceeds nominal limits for valid sensor reading |
|
| 35 | ANALOG 5 HI ALRM | Analog Input #5 has gone above maximum alarm limit |
|
|
| FUEL LVL HI ALRM | Fuel Level |
|
| 36 | ANALOG 5 LO ALRM | Analog Input #5 has gone below minimum alarm limit |
|
|
| FUEL LVL LO ALRM | Fuel Level |
|
| 37 | ANALOG 5 HI WARN | Analog Input #5 has gone above maximum warning limit |
|
|
| FUEL LVL HI WARN | Fuel Level |
|
| 38 | ANALOG 5 LO WARN | Analog Input #5 has gone below maximum warning limit |
|
|
| FUEL LVL LO WARN | Fuel Level |
|
| 39 | ANALOG 5 FAULT | Analog Input #5 sensor exceeds nominal limits for valid sensor reading |
|
|
| FUEL LVL FAULT | Fuel Level |
|
| 40 | ANALOG 6 HI ALRM | Analog Input #6 has gone above maximum alarm limit |
|
|
| FUEL PRS HI ALRM | Fuel Pressure |
|
|
| INLT TMP HI ALRM | Inlet Air Temperature |
|
| 41 | ANALOG 6 LO ALRM | Analog Input #6 has gone below minimum alarm limit |
|
|
| FUEL PRS LO ALRM | Fuel Pressure |
|
|
| INLT TMP LO ALRM | Inlet Air Temperature |
|
|
|
|
|
|
42