Generac Power Systems H-100 technical manual Service, General Information

Models: H-100

1 52
Download 52 pages 43.79 Kb
Page 19
Image 19
SERVICE

General Information

H-100 Control Panel Technical Manual

“Warmed Up, Alarms On”

SERVICE

Generator is started, warmed up, and the hold-off alarms are enabled.

“Running,cooling down”

Generator is still running, but waiting for cool down timer to expire.

“Stopping”

Generator is running down after being turned off normally.

“Stopping due to Alrm”

Generator is running down after being turned off due to a shutdown alarm.

“Stopped due to Alarm”

Generator is stopped due to a shutdown alarm.

LINE 3: System Time and Date. It is able to be changed on this page by using the arrow buttons to go from field to field or to modify a field in edit mode and the “ENTER” button to enter and exit edit mode. There are five editable fields: Hours, Minutes, Month, Day, and Year. The day of the week will change as the displayed date is changed. See the “SET DATE AND TIME” section of this manual for details.

LINE 4: “More” field to allow page selection.

Press the “ENTER” button.

There are four Maintenance Status pages. The first three pages show the status of the scheduled mainte- nance items. The fourth page allows changing of the display contrast.

Do the following to view the service pages:

Press the “MENU” button.

Press the button three times or the button once.

Press the “ENTER” button.

This is a typical second System Status page.

LINE 1: Firmware and Hardware release versions.

LINE 2: Configuration File identifier – serial num- ber, model number, or text.

LINE 3: ILC program name. This text string is blank or blocks (as shown above) when there is no ILC program loaded.

LINE 4: ILC program running status followed by the “More” field to allow page selection.

This is a typical first Maintenance Status page. Each line displays a maintenance item that has been set up via GenLink. The value displayed is the approxi- mate % of life remaining before maintenance should be performed. Refer to the Maintenance setup using GenLink.

Press the “ENTER” button.

This is a typical second Maintenance Status page.

17

Page 19
Image 19
Generac Power Systems H-100 technical manual Service, General Information