Generac Power Systems H-100 technical manual Status, General Information

Models: H-100

1 52
Download 52 pages 43.79 Kb
Page 18
Image 18
STATUS

General Information

H-100 Control Panel Technical Manual

STATUS

There are two System Status pages. These pages show the system status, system time, and system versions.

Do the following to view the system status pages:

Press the “MENU” button.

Press the button twice.

Press the “ENTER” button.

This is a typical first System Status page.

LINE 1: Engine Running Status. It can have the fol- lowing values:

“Stopped, Key SW Off”

The engine is stopped and the key switch is in the OFF position.

“Running from Manual”

The engine is starting or running and the key switch is in the MANUAL position.

“Running from 2-wire”

The engine is starting or running because the 2-wire start signal was activated and the key switch is in the AUTO position.

“Running from serial”

The engine is starting or running because the GenLink commanded it to start and the key switch is in the AUTO position.

“Running exercise”

The engine is starting or running because internal exercise was activated and the key switch is in the AUTO position.

“Stopped, Key SW Auto”

The engine is stopped and the key switch is in the AUTO position.

“Running, QuietTest”

The engine is starting or running because QuietTest® was activated and the key switch is in the AUTO posi- tion.

“Running, HTS Xfer SW”

The engine is starting or running because the HTS(s) indicated a need for the generator power and the key switch is in the AUTO position.

LINE 2: Generator Status. It can have the following values:

“Resetting”

The generator control system is resetting.

“Stopped”

Generator is stopped and not preheating.

“Stopped, Preheating “

Generator is stopped and preheating.

“Cranking”

Generator is starting and not preheating.

“Cranking, Preheating”

Generator is starting and preheating.

“Pause between starts”

Generator is pausing between consecutive start attempts.

“Started,not to speed”

Generator is started, but has not attained normal running speed yet.

“Warming, Alarms Off “

Generator is started and is up to speed, but is waiting for warmup timer to expire.

“Warmed Up,Alarms Off”

Generator is started and warmed up, but the hold-off alarms are not yet enabled.

“Warming, Alarms On”

Generator is started and the hold-off alarms are enabled, but is waiting for warmup timer to expire.

16

Page 18
Image 18
Generac Power Systems H-100 technical manual Status, General Information