ENABLE GENERAC COMMERCIAL TRANSFER SWITCH (HTS)

General Information

H-100 Control Panel Technical Manual

Use the arrow buttons to change the contrast value (range is 00 to 37). Pressing the “HOME” button while in edit mode will return the value to the last entered value.

Press the “ENTER” button to exit edit mode.

The contrast is now set and can only be changed by editing the value on this page.

ENABLE GENERAC COMMERCIAL TRANSFER SWITCH (HTS)

The H-100 Control Panel can control up to four HTSs via the RS-485 communications port. The H-100 Control Panel is shipped without the HTS control enabled. If the user has an HTS in their system, they must enable the HTS via GenLink or the front panel. If the HTS is not enabled, the generator will not operate automatically with loss of utility. If the H-100 Control Panel enables a non-existent HTS, there will be a warning indicated.

NOTE:

Non-HTS switches use the two-wire start inter- face and do not need enabling by H-100 Control Panel.

‹HTS SETUP USING GENLINK

Connect to the H-100 control panel.

Using the “Configuration” pull down, select “Transfer Switch Configuration” to display the HTS Configuration screen.

The lower left corner contains the HTS number. Use the “Prev” and “Next” buttons to select the appro- priate switch number - 1 through 4. If enabling the switch, check the “Switch Connected” check box in the middle of the screen. If disabling the switch, uncheck the “Switch Connected” check box. The remainder of the settings on this page are described in the HTS manual.

‹HTS SETUP USING FRONT PANEL

Press the “MENU” button.