Appendix B
| Number | Default Function Name | Function Description |
|
| 42 | ANALOG 6 HI WARN | Analog Input #6 has gone above maximum warning limit |
|
|
| FUEL PRS HI WARN | Fuel Pressure |
|
|
| INLT TMP HI WARN | Inlet Air Temperature |
|
| 43 | ANALOG 6 LO WARN | Analog Input #6 has gone below maximum warning limit |
|
|
| FUEL PRS LO WARN | Fuel Pressure |
|
|
| INLT TMP LO WARN | Inlet Air Temperature |
|
| 44 | ANALOG 6 FAULT | Analog Input #6 sensor exceeds nominal limits for valid sensor reading |
|
|
| FUEL PRS FAULT | Fuel Pressure |
|
|
| INLT TMP FAULT | Inlet Air Temperature |
|
| 45 | ANALOG 7 HI ALRM | Analog Input #7 has gone above maximum alarm limit |
|
|
| GOV POS HI ALARM | Throttle Position |
|
| 46 | ANALOG 7 LO ALRM | Analog Input #7 has gone below minimum alarm limit |
|
|
| GOV POS LO ALARM | Throttle Position |
|
| 47 | ANALOG 7 HI WARN | Analog Input #7 has gone above maximum warning limit |
|
|
| GOV POS HI WARN | Throttle Position |
|
| 48 | ANALOG 7 LO WARN | Analog Input #7 has gone below maximum warning limit |
|
|
| GOV POS LO WARN | Throttle Position |
|
| 49 | ANALOG 7 FAULT | Analog Input #7 sensor exceeds nominal limits for valid sensor reading |
|
|
| GOV POS FAULT | Throttle Position |
|
| 50 | ANALOG 8 HI ALRM | Analog Input #8 has gone above maximum alarm limit |
|
|
| OXYGEN HI ALARM | Emissions Sensor |
|
|
| FLUID BS HI ALRM | Fluid Basin |
|
| 51 | ANALOG 8 LO ALRM | Analog Input #8 has gone below minimum alarm limit |
|
|
| OXYGEN LO ALRM | Emissions Sensor |
|
|
| FLUID BS LO ALRM | Fluid Basin |
|
| 52 | ANALOG 8 HI WARN | Analog Input #8 has gone above maximum warning limit |
|
|
| OXYGEN HI WARN | Emissions Sensor |
|
|
| FLUID BS HI WARN | Fluid Basin |
|
| 53 | ANALOG 8 LO WARN | Analog Input #8 has gone below maximum warning limit |
|
|
| OXYGEN LO WARN | Emissions Sensor |
|
|
| FLUID BS LO WARN | Fluid Basin |
|
| 54 | ANALOG 8 FAULT | Analog Input #8 sensor exceeds nominal limits for valid sensor reading |
|
|
| O2 SENSOR FAULT | Emissions Sensor |
|
|
| FLUID BS FAULT | Fluid Basin |
|
| 55 | ANALOG 9 HI ALRM | Analog Input #9 has gone above maximum alarm limit |
|
|
| CHG CURR HI ALRM | Battery Charge Current |
|
| 56 | ANALOG 9 LO ALRM | Analog Input #9 has gone below minimum alarm limit |
|
|
| CHG CURR LO ALRM | Battery Charge Current |
|
| 57 | ANALOG 9 HI WARN | Analog Input #9 has gone above maximum warning limit |
|
|
| CHG CURR HI WARN | Battery Charge Current |
|
| 58 | ANALOG 9 LO WARN | Analog Input #9 has gone below maximum warning limit |
|
|
| CHG CURR LO WARN | Battery Charge Current |
|
| 59 | ANALOG 9 FAULT | Analog Input #9 sensor exceeds nominal limits for valid sensor reading |
|
|
| CHG CURR FAULT | Battery Charge Current |
|
| 60 | BAT VOLT HI ALRM | Battery Voltage has gone above maximum alarm limit |
|
| 61 | BAT VOLT LO ALRM | Battery Voltage has gone below minimum alarm limit |
|
| 62 | BAT VOLT HI WARN | Battery Voltage has gone above maximum warning limit |
|
43