Storage & Service

Storage

First turn your UPS OFF and disconnect its power cord from the wall outlet. Then disconnect all equipment to avoid battery drain. If you plan to store your UPS for an extended period of time, fully recharge the UPS batteries once every three months by plugging the UPS into a live AC outlet, turning the Power Switch ON and letting the UPS charge for 4-6 hours. If UPS batteries remain uncharged for an extended period of time, they will suffer permanent loss of capacity.

Service

If returning your UPS for service, contact your local Tripp Lite dealer or distributor. They will refer you to a service center. Please carefully pack the UPS using the ORIGINAL PACKING MATERIAL that came with the unit. Enclose a letter des-cribing the symptoms of the problem. If the UPS is within the 2 year warranty period, enclose a copy of your sales receipt.

Specifications

Model

SmartPro 450 RTI

Output Capacity (VA/Watts):

450/270

Battery Runtime (Half Load/Full Load) Minutes:

12/3

Typical Runtime (Desktop PC/15 in. monitor) Minutes:

20

Battery Recharge Time:

2-4 hrs.

Approvals:

CE

Input Voltage (230V); Input Frequency (50/60 Hz, Auto-Selecting); On-Line Input Voltage Range (187-280 volts); Voltage-Regulated Output Voltage Range (230V +6%/-12%); On-Battery Output Voltage Range (230V ±5%); Output Waveform Line Mode (filtered sinewave); Output Waveform Battery Mode (PWM sine wave); AC Surge Suppression (exceeds IEEE 587 Cat. A standards); AC Noise Attenuation (>40 dB); AC TVSS Protection Modes (H to N, H to G, N to G).

The policy of Tripp Lite is one of continuous improvement. Specifications are subject to change.

Wire Color

Wire 1

Wire 2

Wire 3

American

Black

White

Green

European

Brown

Blue

Green/Yellow

Wire Reference

Wire 1

Wire 2

Wire 3

American

Line 1

Neutral

Ground

European

Line 1

Line 2 or Neutral

Ground

Page 8
Image 8
Tripp Lite 450 RTI specifications Storage & Service, Specifications