Configuration continued
• Equalize Battery Charge (DIP Switch #3, Group B)
This DIP Switch is momentarily engaged to begin the process of equalizing the internal resistance of your battery’s cells. This can extend the useful life of certain types of batteries; consult with your battery's manufacturer to determine if your batteries could benefit from this process. The charge equalization process is automatic and once started can only be stopped by removing the input power.
Setting Procedure
•Move to “Equalize” (DOWN) position for three seconds.
•Move to “Reset” (UP) position and leave it there.
CAUTION: Battery charge equalization should only be performed in strict accordance with the battery manufacturer’s instructions and specifications.
CAUTION: Do not leave DIP switch #3 in the down position after beginning process.
Battery Charge | Switch Position |
ResetUp*
EqualizeDown
* Factory default setting.
4 3 2 1 Reset*
Equalize
•Limit Battery Charger (DIP Switch #4, Group B) (APSINT1524 only)
To prevent overheating smaller batteries, the charger on this UPS system is initially set to deliver only a fraction of its maximum power rating to connected batteries. If you are using this system with a larger (over 100
Battery Charger | Switch Position |
Partial (1/3) Charging Power | Up* |
Full Charging Power | Down |
* Factory default setting. |
|
4 3 2 1 Partial*
Full
7