6 – Standard Operation continued

6-4 Battery Mode Startup (Cold Start)

The UPS system supports battery mode startup (cold start), allowing it to operate as a standalone power source when AC input power is unavailable.

1.Make sure the UPS system is properly installed and the battery is at least partially charged.

2.Some electronic equipment may draw more amps during startup; consider reducing the initial load on the UPS system.

3.Press the ON button for approximately 5 seconds, then release it. The UPS will beep twice and the LCD screen will change from A to G .

4.Press the ON button again for approximately 3 seconds, then release it. The UPS will beep twice and the LCD screen will change from G to H . (The UPS system will remain awake for approximately 15 seconds after completing the previous step. If you do not press the ON button again before 15 seconds have elapsed, you will need to repeat the previous step.)

5.The UPS system will run a self-test and display H again. Battery mode startup is successful and connected equipment will operate until the battery is depleted (or until pre-defined shutdown parameters have been reached).

G

 

H

This screen indicates the UPS inverter is off and utility input is abnormal.

This screen shows the utility input voltage is zero.

6-5 UPS System Shutdown

1.Press the OFF button for approximately 5 seconds, then release it. The inverter output will turn off and the LCD screen will show B .

2.Turn off the UPS system’s utility input breaker.

3.The UPS system is now completely off. If the UPS system will be turned off for a significant length of time, follow the battery recharging instructions in Section 11 – Storage and Service.

B

This screen indicates the UPS inverter is off.

6-6 UPS System Settings and Measurements

Checking UPS System Measurements

To check the values measured by the UPS, scroll up or down through the LCD panel. Scrolling down will display values in the following order:

I

 

L

 

O

 

Bypass Input Voltage

 

Output Voltage

 

Battery Voltage

 

 

 

 

 

J

 

M

 

P

 

 

Utility Input Frequency

 

Output Frequency

Inner Temperature (°C)

 

 

 

 

K

 

N

 

 

Bypass Input Frequency

Output Load Percentage

13

Page 13
Image 13
Tripp Lite SU10KRT3/1X Battery Mode Startup Cold Start, UPS System Shutdown, UPS System Settings and Measurements

SU10KRT3/1X specifications

The Tripp Lite SU10KRT3/1X is a robust and efficient 10kVA UPS (Uninterruptible Power Supply) designed to meet the power management needs of critical electronic equipment. This industrial-grade UPS is ideal for safeguarding servers, telecommunications equipment, and networking hardware, providing the reliability necessary in today's tech-dependent world.

One of the standout features of the SU10KRT3/1X is its ability to deliver pure sine wave output, which ensures that connected devices receive a stable and clean power supply. This is especially crucial for sensitive electronics, including servers and other IT infrastructure components that require a consistent power source to maintain peak performance and operational integrity.

The UPS boasts a comprehensive input voltage range, making it adaptable to various power conditions. With an output power factor of 0.9, the SU10KRT3/1X maximizes the power available for connected devices, providing efficient power usage that ultimately lowers operational costs. This UPS also features an automatic voltage regulation (AVR) system that stabilizes voltage fluctuations, offering an additional layer of protection against surges and brownouts.

Another significant characteristic of the Tripp Lite SU10KRT3/1X is its modular design, featuring hot-swappable batteries that allow for easy maintenance without shutting down connected equipment. This feature minimizes downtime and enhances reliability, ensuring that critical systems remain functional even during maintenance activities.

The LCD display provides real-time status information, including input and output voltage, battery status, and load levels. This user-friendly interface allows IT administrators and technicians to monitor the UPS easily and respond quickly to any potential issues.

Compatibility is another area where the SU10KRT3/1X excels. It is equipped with multiple communication options, including USB, RS-232, and optional SNMP capability, enabling seamless integration with monitoring systems and ensuring effective communication with connected devices.

Tripp Lite has backed the SU10KRT3/1X with a solid warranty and exceptional customer support, assuring users of the product's reliability and performance. As organizations increasingly rely on technology, the SU10KRT3/1X serves as a trustworthy solution for maintaining consistent power availability, ultimately contributing to business continuity and efficiency.