Installation continued

Installation continued

 

 

 

Connecting the PDU continued

 

 

 

2-1Connect Input Plug Adapters (Optional -

 

 

 

Model PDUMH20ATNET Only): The PDU

 

 

 

includes two adapters that convert one or both

 

 

 

of the L5-20P input plugs to 5-20P input plugs.

2-1

 

PDUMH20ATNET

Connecting the adapters is optional. The PDU

 

 

 

 

will function normally without connecting the

 

 

 

adapters.

 

 

 

2-2Connect Secondary Input Cord to PDU:

 

 

 

Although the PDU will operate without

 

 

 

connecting the Secondary input cord, the

2-2

PDUMH15ATNET

PDUMH20ATNET

Secondary input is required for the PDU's

 

 

 

Automatic Transfer Switch function.

 

 

 

2-3Connect PDU Input Plugs: Connect the

 

 

 

Primary input plug A to a preferred source of

 

 

 

grounded 120V AC power, such as a

 

A

 

SmartOnlineUPS System. The UPS system

 

 

must not share a circuit with a heavy electrical

 

 

 

load (such as an air conditioner or refrigerator).

 

B

PDUMH15ATNET

Under normal operating conditions, the PDU

 

 

 

 

will distribute AC power from the Primary

 

 

 

input source. Connect the Secondary input plug

 

 

 

B to an alternative source of grounded 120V

 

 

 

AC power, such as a redundant SmartOnline

 

 

 

UPS System. The UPS system must not share a

 

 

 

circuit with a heavy electrical load (such as an

 

 

A

air conditioner or refrigerator). Do not plug the

 

 

 

 

 

Secondary input into the same power source as

 

 

 

the Primary input. The PDU will distribute AC

 

 

 

power from the Secondary input only if the

 

B

PDUMH20ATNET

Primary input becomes unavailable. See the

 

 

 

 

Configuration and Operation section for more

 

 

 

information.

 

 

 

Note: Immediately after the PDU is connected to live AC

2-3

 

 

power, you may notice a series of soft clicking sounds emitted

 

 

by electrical relays within the PDU. The relays may also click

 

 

 

occasionally during the operation of the PDU. This is normal.

 

 

PDUMH15ATNET

3 Connect Equipment to PDU: Do not exceed

 

 

 

 

 

the load rating of the PDU. The total electrical

 

 

 

current used by the PDU will be displayed on

 

 

 

the digital meter in amperes. Each outlet

 

 

 

includes a green LED that illuminates when the

 

 

 

outlet is receiving AC power.

 

 