Tripp Lite PDUMH20HVNET owner manual Connecting the PDU

Models: PDUMH20HVNET

1 11
Download 11 pages 43.68 Kb
Page 4
Image 4

Installation continued

Connecting the PDU

2-1NEMAAdapter Connection (Optional - PDUMH20HVNET Only): The PDUMH20HVNET includes a plug adapter that adds a NEMA L6-20P plug to the input power cord. Use this adapter only if you will be connecting the PDUMH20HVNET to a NEMA L6-20R outlet. Insert the IEC 60320 C19 connector A of the adapter into the IEC 60320 C20 connector B of the input power cord. Secure the connection with the retention bracket C by using the included bolts to fasten the two halves of the bracket around the connection as shown. Caution: To avoid the risk of electric shock, ensure that the Neutral (L2) conductor has been identified before connecting the PDU.

2-2Input Power Cord Connection: Insert the IEC 60320 C19 (PDUMH20HVNET) or IEC 60320 C13 (PDUMH15HVNET) connector A

of the input power cord into the IEC 60320 C20 (PDUMH20HVNET) or IEC 60320 C14

(PDUMH15HVNET) inlet B of the PDU. Connect the other end of the input power cord

Cto a compatible source of AC power, such as a UPS system, PDU or utility outlet. The PDU should be provided with over-current protection: PDUMH20HVNET should be provided with a maximum 20A branch-rated over-current protection device; PDUMH15HVNET should be provided with a maximum 15A branch-rated over-current protection device.

Note: The AC power source should not share a circuit with a heavy electrical load (such as an air conditioner or refrigerator).

2-3Equipment Power Cord Connection: Insert the IEC 60320 C14 connectors A of the equipment power cords into the IEC 60320 C13 output receptacles B of the PDU. The LED C near each output receptacle illuminates when the receptacle is ready to distribute live AC power. The digital load meter D will display the total connected equipment load in amps.

2-4Cord Retention (Optional): If you

 

attached the cord retention shelf in step 1-6 ,

 

tie the input power cord and each equipment

 

power cord to the retention shelf. Attach each

 

cord to the retention shelf by looping the cord

 

and securing it to an attachment point with one

 

of the included cable ties. Make sure that each

 

cord can be unplugged from the PDU without

 

removing the cable tie.

4

 

 

C

 

A

2-1

B

 

 

 

8 8

B

C

 

 

 

A

 

 

 

 

 

PDUMH15HVNET

 

 

 

 

8 8

 

B

A

 

 

 

 

C

 

 

 

2-2PDUMH20HVNET

 

 

 

 

 

B

 

 

 

 

 

 

15

2-3

A

C

 

D

2-4

Page 4
Image 4
Tripp Lite PDUMH20HVNET owner manual Connecting the PDU

PDUMH20HVNET specifications

The Tripp Lite PDUMH20HVNET is a robust power distribution unit (PDU) designed to enhance the efficiency and reliability of data centers and IT environments. This PDU is particularly valuable for those needing remote management capabilities, as it combines advanced features with a versatile design to meet various power distribution needs.

One of the primary characteristics of the PDUMH20HVNET is its ability to support high voltage applications. With an input voltage range of 200-240V, it is compatible with various high-performance equipment. The unit provides a total of 20 amps of power, making it suitable for powering multiple devices while ensuring efficient load balancing across the outlets.

The PDUMH20HVNET features 20 NEMA 5-15R output receptacles, allowing for the connection of multiple devices without sacrificing performance. This distribution unit offers both horizontal and vertical mounting options, granting flexibility for any rack-mounted equipment. Its compact design enables it to fit easily into standard 19-inch racks, saving valuable space in crowded server rooms.

Another notable feature of the PDUMH20HVNET is its built-in network management capabilities. It comes equipped with an Ethernet port that allows for remote monitoring and management via a web interface. Users can track real-time data regarding current loads, voltage, and environmental conditions, enabling proactive management of power resources. This feature is essential for maintaining optimal performance and preventing overload situations.

The unit also includes advanced features like automatic alerts for power fluctuations, allowing for quick responses to any issues that may arise. Additionally, it supports SNMP for seamless integration with existing network management systems, simplifying the overall monitoring process.

Durability and safety are other key aspects of the PDUMH20HVNET. It is constructed with high-quality materials to withstand the rigors of daily use in demanding environments. The built-in surge protection safeguards connected devices from spikes and surges, ensuring the longevity of critical equipment.

In summary, the Tripp Lite PDUMH20HVNET is a feature-rich power distribution unit that delivers reliable performance and remote management capabilities. Its high voltage support, flexible mounting options, and advanced monitoring features make it an essential component for modern data centers and IT operations, contributing to efficient and safe power management.