Features

Features

Circuit Breaker (All Models)

If the current draw of the equipment connected to your model exceeds your model’s circuit breaker rating (15 or 20 amps; see Specifications) for longer than a few seconds, the circuit breaker will trip to prevent any possible damage. When the circuit breaker trips, its plunger will be extended. Remove excess equipment and allow the breaker to cool one minute before depressing its plunger to reset the breaker.

Illuminated “On/Off” Switch (All Models)

When your model is plugged into an AC outlet providing power of appropriate voltage and frequency (see specifications), this switch will illuminate RED when moved to the “ON” position. This indicates 120V AC power is present at the model’s AC receptacles.

Diagnostic Indicator Lights (ISOBAR Models Only)

When your surge suppressor is plugged into an AC outlet providing power of appropriate voltage and frequency (see Specifications), the three LEDs on the front panel show current power conditions as follows, from left to right across the front of the unit:

Line “OK” (Green LED): Indicates that nominal AC power is present with no wiring faults detected. When this LED is illuminated, AC power is safe for connected equipment.

Line Fault (Red LED): Indicates a wiring fault has been detected. If this LED illuminates at any time the unit is plugged in, the fault should be repaired by a qualified electrician as soon as possible. This LED indicates that phases are reversed, ground is missing or some other sort of wiring error exists in the circuit the ISOBAR is plugged into. The Line Fault detector circuitry will identify most common wiring faults, but will not necessarily detect every possible type of fault.

If the Line Fault indicator light illuminates, carefully check the AC receptacle the ISOBAR is plugged into. The receptacle must be tight and securely grounded. A loose AC receptacle may cause the Line Fault LED to illuminate. It must be understood that this Red LED indicates the presence of a wiring fault, but does not indicate the exact nature of the fault.Therefore, a qualified electrician should make necessary repairs.

If the Line Fault indicator light illuminates and power is not present at the outlets, the ISOBAR’s surge-suppression components have been compromised as a result of surge damage. For service, call Tripp Lite Customer Support at (773) 869-1234.

Fully explain the perceived problem to the customer support person. They will either remedy the problem over the phone or give you instructions about return, repair or exchange.

Protection Present (Green LED): Indicates the surge-suppression components are intact and providing full protection against spikes and surges. This LED should be lit anytime the ISOBAR “ON/OFF” switch is turned ON and power is present, as indicated by the lighted power switch. If the Protection Present LED does not light, then some of the surge suppression components are not functioning and the unit should be returned for repair as soon as possible. You may still use the unit; however, connected equipment will be protected from spikes and surges at a lesser level than normal.

ISOLATED FILTER BANKS & CASCADE CIRCUITRY

(IBAR12 and ISOBAR12ULTRA Models Only)

Isolated Filter Banks prevent equipment plugged into each filter bank from interacting with equipment plugged into the other filter bank. Cascade Circuitry provides different levels of protection between the Isolated Filter Banks.

There are two Isolated Filter Banks on IBAR12 and ISOBAR12ULTRA models. Isolated Filter Bank #2, the white outlets on these models’ rear panel, provides the highest level of protection for your most sensitive equipment. Isolated Filter Bank #1, the black outlets on these models’ front and rear panels, provides standard protection for your less-sensitive or noise-producing equipment.

2

Specifications

Model:

IBAR12

ISOBAR12ULTRA

IBAR12/20ULTRA

Series:

AGIB120V12SSRM

AGIB120V12SSRM

AGIB120V20SSRM

AC Energy Absorption (joules):

1280

1280

1280

Surge Suppression (amp spikes)*:

60,000

96,000

96,000

UL 1449 Let-Through Rating:

400V

330V

330V

HF Noise Suppression (@ 1 MHz)

 

 

 

Filter Bank #1:

40 dB

40 dB

80 dB

Filter Bank #2:

80 dB

80 dB

AC Receptacles:

2 NEMA 5-15R (front)

2 NEMA 5-15R (front)

2 NEMA 5-15R (front)

 

10 NEMA 5-15R (back)

10 NEMA 5-15R (back)

10 NEMA 5-15/20R (back)

AC Line Cord:

15', w/NEMA 5-15P plug

15', w/NEMA 5-15P plug

15', w/NEMA 5-20P plug

Circuit Breaker (Resettable):

15 amp

15 amp

20 amp

Dimensions (HxWxD, inches):

1.7 × 17.3 × 3.4

1.7 × 17.3 × 3.4

1.7 × 17.3 × 3.4

Weight (lbs.):

4.6

5.0

5.4

Model:

IBAR12-20T

RS-1215

RS-1215-20

Series:

AGIB120V20SSRM

AGIP120V6IPRM

AGIP120V20RM

AC Energy Absorption (joules):

1280

NONE

NONE

Surge Suppression (amp spikes):

96,000

NONE

NONE

UL 1449 Let-Through Rating:

330V

HF Noise Suppression (@ 1 MHz)

 

 

 

Filter Bank #1:

80 dB

NONE

NONE

Filter Bank #2:

NONE

NONE

AC Receptacles:

2 NEMA 5-15R (front)

6 NEMA 5-15R (front)

6 NEMA 5-20R (front)

 

10 NEMA 5-15/20R (back)

6 NEMA 5-15R (back)

6 NEMA 5-20R (back)

AC Line Cord:

15', w/L5-20P plug

15', w/NEMA 5-15P plug

15', w/NEMA 5-20P plug

Circuit Breaker (Resettable):

20 amp

15 amp

20 amp

Dimensions (HxWxD, inches):

1.7 × 17.3 × 3.4

1.7 × 17.3 × 3.4

1.7 × 17.3 × 3.4

Weight (lbs.):

5.4

4.6

4.6

Model:

RS-1215-RA

RS-1215-HG

DRS-1215

Series:

AGIP120V6IPRM

AGIP120V6IPRM

AGIB120V12LCRM

AC Energy Absorption (joules):

NONE

NONE

1050

Surge Suppression (amp spikes):

NONE

NONE

36,000

UL 1449 Let-Through Rating:

330V

HF Noise Suppression (@ 1 MHz)

 

 

 

Filter Bank #1:

NONE

NONE

NONE

Filter Bank #2:

NONE

NONE

NONE

AC Receptacles:

6 NEMA 5-15R (front)

6 15A hospital grade (front)

6 NEMA 5-15R (front)

 

6 NEMA 5-15R (back)

6 15A hospital grade (back)

6 NEMA 5-15R (back)

AC Line Cord:

15', w/NEMA 5-15P plug

15', w/15A hospital grade plug 15', w/NEMA 5-15P plug

Circuit Breaker (Resettable):

15 amp

15 amp

15 amp

Dimensions (HxWxD, inches):

1.7 × 17.3 × 3.4

1.7 × 17.3 × 3.4

1.7 × 17.3 × 4

Weight (lbs.):

4.6

4.6

4.6

* Spike protection is provided in all three modes: hot to neutral, hot to ground and neutral to ground.

All Models: Nominal Input Voltage: 120VAC; Input Frequency: 50/60 Hz

All ISOBAR Models: Transient Response Time: Instantaneous (0 ns). Transient amplitude reduction occurs faster than the clamp response of the varistors because of the high rejection rate of the ISOBAR filter networks.

UL 1449 (1999 rev.): ISOBAR12ULTRA, IBAR12/20ULTRA, IBAR12-20T and DRS-1215:

330V let-through (UL’s best rating for surge suppression); IBAR12: 400V let-through

UL 1283: All ISOBAR models, for line-noise filtering

CUL: meets Canadian National Standards as certified by UL