Tripp Lite SMX2200XLRT2U Other UPS Features Rear Panel, Basic Operation continued, IEC320

Models: SMX2200XLRT2U

1 60
Download 60 pages 10.09 Kb
Page 9
Image 9
Other UPS Features (Rear Panel)

Basic Operation continued

Other UPS Features (Rear Panel)

IEC320-

C13/230V

AC Receptacles: Your UPS features IEC320-C13 outlets. These output receptacles provide your connected equipment with AC line power during normal operation and battery power during blackouts and brownouts. The UPS protects equipment connected to these receptacles against damaging surges and line noise. If you have a serial or USB connection to your UPS, you can remote- ly reboot connected equipment by turning individually controllable receptacles OFF and ON using Tripp Lite's PowerAlert Software. Three receptacles, labeled LOAD 1, LOAD 2 and LOAD 3, are individually controllable and may be remotely switched OFF and ON using PowerAlert Software without interrupting power to equipment connected to other outlets. Outlets labeled UNSWITCHED may not be remotely turned off. Unswitched outlets can only be turned off by turning off all output receptacles. See software instructions for details.

Communications Ports (USB or RS-232): These ports connect your UPS to any workstation or server. Use with Tripp Lite’s PowerAlert Software and included cables to enable your computer to automatically save open files and shut down equipment during a blackout. Also use PowerAlert Software to mon- itor a wide variety of AC line power and UPS operating conditions. Consult your PowerAlert Software manual or contact Tripp Lite Customer Support for more information. See “USB and RS-232 Serial Communications” in the “Optional Installation” section for installation instructions.

EPO (Emergency Power Off) Port: Your UPS features a EPO port that may be used to connect the UPS to a contact closure switch to enable emergency inverter shutdown. See Optional Installation.

NO EXTERNAL

BATTERIES

EXTERNAL

BATTERIES

Voltage DIP Switches: These switches enable the UPS to be set to match actual input voltage. If the Voltage DIP Switches are set above or below input voltage, the UPS will treat the input as a continuous overvoltage or undervolt- age condition, and will automatically adjust input voltage to match the Voltage DIP Switch setting. This will cause constant, unnecessary wear on the UPS.

Note: The Voltage DIP Switches must be set with the UPS turned OFF and disconnected from utility power. If the switches are set while the UPS is connected to utility power, the setting will not take effect.