INCORRECT CORRECT

Installation (continued)

5-3Insert the exhaust panel into the window opening, then close the window against the exhaust panel. A tight seal will permit maximum cooling efficiency. Note: There must be at least 10 inches (25.4 cm) of open space behind the exhaust panel to allow adequate airflow.

Note: The flexible exhaust duct can extend to a maximum length of 118 inches (300 cm). Provide the straightest, shortest path available. Excessive bending or stretching of the duct will reduce cooling efficiency.

Horizontal Window

Opening

INCORRECT CORRECT

Vertical

Window

Opening

5-3

6Drainage Plug Insertion

Warning: The unit’s built-in re-evaporator will not function until you insert the drainage plug into the drainage outlet.

When the unit cools or dehumidifies, condensation forms. The unit has a built-in re-evaporator that allows it to expel condensation through the warm air exhaust stream. This feature allows the unit to operate indefinitely without requiring you to empty a water collection tank. The unit ships with both the upper and lower drainage plugs pre-installed.

6-1Cooling Mode with Re-Evaporation

Both plugs must remain installed to enable re-evaporation of condensation.

6-2Cooling Mode without Re-Evaporation

To use Cooling mode without re-evaporating condensation, remove the bottom drain plug and route user-supplied drain line to external drainage. The top drain plug must remain installed.

6-3Dehumidify Mode

When using the unit in Dehumidify mode, remove the top drain plug and route user- supplied drain line to external drainage. The bottom drain must remain installed. This will maximize the amount of water removed from the air.

Note: If the drainage system becomes clogged, a small internal reservoir will collect condensation. If the drainage system is not cleared before the internal reservoir fills, the unit will shut down automatically.

Warning: Before connecting the unit to a dedicated drainage system, turn it off and unplug it. There is a risk of electric shock while the unit is plugged in.

Note: If your building’s cooling system has night or weekend thermostat setbacks, has periodic shutdowns, or has limited cooling capacity, you may need to consider alternatives to the standard installation. This product is meant to be used as a supplemental cooling device, and cannot make up for significant fluctuations in building temperature or humidity.

Low Temperature Operation

The SRCOOL12K is a high performance cooler, capable of producing very cold air output. When using the SRCOOL12K in environments that are already cold (20° C / 68° F or less), Tripp Lite recommends using the Dehumidify Mode only. This will allow the unit to continue to provide the supplemental cooling while preventing any evaporator icing issues caused by the low room temperature.

6-1

TO EXTERNAL

DRAIN

6-2

TO EXTERNAL

DRAIN