Operation continued

Bypass Messages

While in Bypass Mode, the UPS monitors its input voltage and passes that input power along to connected equipment. The UPS will not provide battery backup in Bypass Mode.

If the output voltage deviates from an acceptable range (between 15% higher and 20% lower than nominal), the UPS displays the condition on its LCD and stops supplying output power to its load. If power levels return to an acceptable level, the UPS resumes supplying power to the load, and its LCD reports that output voltage was too high or too low at one time, but has returned to nominal.

 

 

BYPASS VOLTAGE

 

LCD DISPLAY

 

 

 

 

CONDITIONS

 

MESSAGES

 

 

 

 

 

 

 

 

 

 

 

>15% Higher

 

 

 

 

 

 

 

NO OUTPUT

 

 

 

 

Than Nominal

 

BYPASS AC TOO HI

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

>20% Lower

 

 

 

 

 

 

 

NO OUTPUT

 

 

 

 

Than Nominal

 

BYPASS AC TOO LO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Was Too High,

 

BYPASS MODE

 

 

 

 

Now Nominal

 

BYPASS AC WAS HI

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Was Too Low,

 

BYPASS MODE

 

 

 

 

Now Nominal

 

BYPASS AC WAS LO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Shutdown Messages

Your UPS will shut down and the LCD will display a message if it detects one of the following conditions. Note: During all these conditions, the “Input,” “Output” and “Bypass” LEDs will be illuminated.

 

SHUTDOWN

 

LCD DISPLAY

 

 

CONDITIONS

 

MESSAGES

 

 

 

 

 

 

 

 

 

 

 

 

Extended

 

SHUT DOWN

 

 

Overload

 

OVERLOAD XXX%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output Short

 

SHUT DOWN

 

 

Circuit

 

O/P SHORT CIRCUIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote Shutdown

 

SHUT DOWN

 

 

Command (Via DB9)

 

REMOTE COMMAND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote Shutdown

 

SHUT DOWN

 

 

Command (Via EPO)

 

EMERGENCY STOP!

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Internal

 

SHUT DOWN

 

 

Faults

 

+ DC BUS HIGH

 

 

 

 

 

 

 

 

 

SHUT DOWN

 

 

 

 

+ DC BUS LOW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHUT DOWN

 

 

 

 

- DC BUS HIGH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHUT DOWN

 

 

 

 

- DC BUS LOW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHUT DOWN

 

 

 

 

OVERTEMPERATURE

 

 

 

 

 

 

 

 

 

 

 

18

Page 18
Image 18
Tripp Lite SU10KRT3U, SU6000RT3UXR owner manual Bypass Messages, Shutdown Messages, Conditions Messages