Operation (continued)

Output Voltage Selection

The UPS output voltage is set at 208/120V~ when the UPS is shipped from the factory. In order to change the output voltage of the UPS, you first need to enter “ON BATTERY MODE” by cold-starting the UPS. (The battery must be at least partially charged for this operation to succeed.) If the UPS is on, press and hold the “OFF” button until you hear a beep, disconnect any connected equipment and disconnect the UPS from its AC power input. After the UPS is disconnected from AC power, press the “ON/MUTE” button until you hear a beep. The LCD screen will show “ON BATTERY MODE” and an alarm will sound periodically to inform you that the UPS is using battery power. Silence the alarm by pressing the “ON/MUTE” button.

After the UPS has entered “ON BATTERY MODE”, press the SCROLL UP and SCROLL DOWN buttons simultaneously for longer than 1 second. The UPS will beep and the LCD will show the SET-UP screen (1). Press the SCROLL UP/SELECT button to enter the “UPS SET-UP” procedure (2). Press the SCROLL UP/SELECT button again to enter the “OUTPUT SELECT” procedure (3). There are 3 output voltage selections. Press the SCROLL DOWN button to scroll to the desired output voltage selection (3)-(5) and then press the SCROLL UP/SELECT button to select it. The LCD will return to the “OUTPUT SELECT” screen (2). Press the SCROLL DOWN button to reach the SET-UP screen

(1)and press the SCROLL DOWN button again to exit the SET-UP procedure. The LCD should be back to “ON BATTERY MODE”. Press the “OFF” key until you hear a beep, and the UPS will save the selected output voltage parameter. Restore the AC power input of the UPS and press the “ON” key to turn on the UPS and use the SCROLL DOWN button to scroll through the basic power conditions displays and confirm that the output voltage has been changed to the desired value.

Note:

208 / 120V<120D Output Voltage (L1-L2)=208V, Output Voltage (L1,L2)=120V and L1 leads L2 120 degrees 208 / 120V<240D Output Voltage (L1-L2)=208V, Output Voltage (L1,L2)=120V and L2 leads L1 120 degrees 240 / 120V<180D Output Voltage (L1-L2)=240V, Output Voltage (L1,L2)=120V and L1 leads L2 180 degrees

Additional Self-Test

If a self-test is initiated after startup, the LCD will display a message.

 

 

 

 

Self-Test Is Running

 

TESTING BATTERY

 

 

LOAD1 = XXX% X.XKW

 

 

 

 

 

 

 

 

 

 

 

 

12

Page 12
Image 12
Tripp Lite SU16000RT4UHW owner manual Output Voltage Selection, Additional Self-Test

SU16000RT4U, SU16000RT4UHW specifications

The Tripp Lite SU16000RT4UHW is a high-capacity rack-mounted uninterruptible power supply (UPS) designed to provide reliable power protection for critical IT infrastructure. With a maximum output of 16,000 VA, this device is ideal for data centers, server rooms, and enterprise networks that demand continuous power and high performance. One of its standout features is its hybrid design, which allows for versatile installation in both rack and tower formats, making it suitable for various environments.

The SU16000RT4U offers advanced battery management technologies, ensuring long-lasting performance and efficiency. Its scalable architecture allows users to add additional battery packs for extended runtime, which is essential in situations where power outages can disrupt business operations. Equipped with smart features, it includes an LCD control panel that provides real-time information regarding battery status, load level, and other vital metrics, enabling users to monitor performance effortlessly.

Another significant characteristic of the SU16000RT4UHW is its compatibility with Tripp Lite's PowerAlert software. This software allows for advanced management of power conditions and remote monitoring via SNMP interface when paired with the optional SNMP/Web card. The UPS also includes a variety of outlets, including both NEMA and IEC standard configurations, catering to different equipment and ensuring adaptability.

Furthermore, this UPS is designed with enhanced protection features such as spike and surge suppression, which safeguards connected devices from electrical disturbances. The internal smart charging system also maximizes battery life by optimizing charging cycles based on usage patterns. This means that users can expect higher availability and a longer operational lifespan.

Constructed with durability in mind, Tripp Lite has included a fault-tolerant design that ensures uninterrupted power delivery even under extreme conditions. The SU16000RT4UHW's robust thermal management enhances cooling efficiency, contributing to reliable operation even in densely populated rack environments.

In conclusion, the Tripp Lite SU16000RT4UHW and its counterpart the SU16000RT4U are essential components for any organization that prioritizes reliable power management. With its high capacity, advanced features, and flexible configurations, it provides unmatched protection for critical IT equipment, ensuring business continuity in the face of electrical failures. Investing in such technology not only protects hardware but also secures data integrity and operational efficiency.