Tripp Lite SU2200XLA Voltage Regulation, Leds Alarms & Switches, Surge / Noise Suppression

Models: SU2200XLA

1 5
Download 5 pages 63.98 Kb
Page 3
Image 3
Typical battery lifespan

Full load runtime

Half load runtime

Expandable battery runtime

DC system voltage

Typical battery lifespan

Battery recharge rate

Replacement Battery Cartridge

4.5min. with internal batteries (1600W) 14 min. with internal batteries (800W)

Runtime is expandable with BP48V24-2U (limit 1) or BP48V60RT3U (multi-pack compatible) external battery packs

48VDC

3-6 years, depending on usage

Less than 5 hours to 90%

RBC48-SUTWR

VOLTAGE REGULATION

Voltage regulation description

Overvoltage correction

Brownout correction

On-line, double-conversion power conditioning maintains output within 2% of 100/110/120 volts at all times

Maintains output of selected nominal +/-2% during overvoltages to 138V AC

Maintains output of selected nominal +/-2% during undervoltages to 65V AC (at loads greater than 70% undervoltage correction extends to 80V)

LEDS ALARMS & SWITCHES

Front panel LEDs

LED STATUS DISPLAY: line power (green), online (green), bypass (yellow), on battery (green), overload (red), battery low (yellow) - 4 LED LOAD / BATTERY LEVEL DISPLAY (100%, 75%, 50%, 25%). LED display panel easily rotates for better viewing in rackmount or tower configurations.

Alarms

Multi-function audible alarm with distinctive ring patterns offer notification of backup operation (2 sec. on / 0.5 sec. off), low battery warning (1.25 sec. on / 0.5 sec. off), overload (sounds continuously), UPS fault (4.2 sec. on / 1 sec. off), input voltage out of frequency (2.1 sec. on / 0.14 sec. off) and high input voltage (2.1 sec. on 0.07 sec. off)

Switches

Includes power off/on switch to enable system turn on (press ON switch), UPS battery test (press ON switch during normal AC operation), buzzer silence (press ON switch during battery operation) and OFF (press OFF switch) - all switch functions require that the switch be pressed and held for longer than 2 sec. but less than 4 sec.

SURGE / NOISE SUPPRESSION

AC surge

570 joules

suppression

 

 

 

AC suppression

Instantaneous

response time

 

 

 

Dataline

Set of 8 wire RJ-style interface jacks provides surge suppression for network Ethernet or tel/DSL connection. Pins 1,2,3

suppression

and 6 offer Ethernet protection starting at 7.5V and the center two wires, pins 4 & 5, offer tel/DSL line suppression

 

starting at 260V

 

 

EMI / RFI AC noise

Yes

suppression

 

 

 

PHYSICAL

 

Shipping weight

59.5

(lbs)

 

 

 

Shipping weight

27

(kg)

 

 

 

Shipping

15.25 x 13 x 24

Dimensions

 

(HWD/in)

 

 

 

Shipping Dimensions (HWD/cm)

38.7 x 33 x 61

Unit weight (lbs)

Unit weight (kg)

Unit Dimensions (HWD/in)

52.7

23.9

10.25 x 9 x 19.5

Page 3
Image 3
Tripp Lite SU2200XLA warranty Voltage Regulation, Leds Alarms & Switches, Surge / Noise Suppression, Physical