Tripp Lite SU30K3/3 warranty Voltage Regulation, Leds Alarms & Switches, Surge / Noise Suppression

Models: SU30K3/3

1 5
Download 5 pages 55.32 Kb
Page 3
Image 3
VOLTAGE REGULATION

Full load runtime

Half load runtime

Expandable battery runtime

DC system voltage

Typical battery lifespan

Battery recharge rate

Included internal batteries: 5 min. (24,000 watts). Runtime can be extended with additional internal battery packs (model # SURBC2030).

Included internal batteries: 13 min. (12,000 watts). Runtime can be extended with additional internal battery packs (model

# SURBC2030).

Supports extended runtime with optional external battery modules (model # SUBF2030). Build to order expandable runtime systems are also available.

240V DC

3 - 6 years, depending on usage

2 - 4 hours to 90%

VOLTAGE REGULATION

Voltage regulation description

Overvoltage correction

Brownout correction

On-line, double-conversion process gives this UPS the ability to maintain output voltage within +/-2% of nominal voltage at all times

Maintains continuous operation without using battery power during overvoltages to 144 / 250V AC (3-Phase, 4-Wire, wye), reducing output within 2% of nominal

Maintains continuous operation without using battery power during brownout / undervoltage conditions to 88 / 166V AC (3-Phase, 4-Wire, wye)

LEDS ALARMS & SWITCHES

Front panel LEDs

7 LED DISPLAY: AC input, bypass input, AC-DC charger, DC-AC inverter, AC output, bypass operation and battery

operation. SELECTABLE LCD DISPLAY: indicates a wide range of UPS operational and fault/warning conditions including operational mode, alarm/shutdown conditions, input/output voltage/frequency, battery voltage, load percentage and more.

Alarms

Switches

Alarms warn against a variety of operational conditions: low battery, overload, shutdown, bypass and more

"ON" button turns UPS's inverter ON. "OFF" button turns UPS's inverter OFF. "Select" Button browses through items displayed on LCD screen. "Enter" button selects items displayed on LCD screen. "Select" and "Enter" buttons used simultaneously mute UPS alar

SURGE / NOISE SUPPRESSION

AC surge

480 joules

suppression

 

 

 

AC suppression

Instantaneous

response time

 

 

 

EMI / RFI AC noise

Yes

suppression

 

 

 

PHYSICAL

 

Shipping weight

750

(lbs)

 

 

 

Shipping weight

340

(kg)

 

 

 

Shipping

Power Module (44 x 21 x 32), Battery Module (23 x 24 x 40)

Dimensions

 

(HWD/in)

 

 

 

Shipping Dimensions (HWD/cm)

109.2 x 71.1 x 113

Unit weight (lbs)

Unit weight (kg)

Unit Dimensions (HWD/in)

Unit Dimensions (HWD/cm)

Material of construction

662

300

Power Module (34 x 15 x 26), Battery Module (20 x 18 x 36)

Power Module (87 x 38 x 66), Battery Module (51 x 45 x 91)

Steel