Tripp Lite SU6000RT4UHV Frequency compatibility, Output voltage regulation Battery mode, Input

Models: SU6000RT4UHV

1 7
Download 7 pages 62.52 Kb
Page 3
Image 3
Frequency compatibility

Frequency compatibility

Frequency compatibility details

Output voltage regulation (line mode)

Output voltage regulation (Economy line mode)

50/60 Hz (auto-selectable)

Output frequency matches input nominal on startup; Frequency conversion mode enables conversion of 60Hz to 50Hz or 50Hz to 60Hz (no de-rating)

+/- 2%

+/- 10%

Output voltage regulation (Battery mode)

+/- 2%

Built-in UPS output receptacles

Output receptacle details

Output circuit breaker

Output AC waveform (AC mode)

Output AC waveform (battery mode)

INPUT

2 L6-20R outlet(s); 2 L6-30R outlet(s)

Output receptacles and input line cord are mounted on a detachable PDU backplate with bypass switch to enable hot-swappable power module replacement

20A breaker protects L6-20R outlets, L6-30R outlets are unbreakered

Pure Sine wave

Pure Sine wave

Rated input current (at maximum load)

Nominal Input Voltage(s) Supported

Nominal input voltage description

UPS input connection type

UPS Input cord length (ft.)

UPS Input cord length (m)

Recommended Electrical Service

BATTERY

31.9A (200V), 30.6A (208V), 29A (220V), 27.7A (230V), 26.6A (240V)

200V AC; 208V AC; 220V AC; 230V AC; 240V AC

Factory configured to 208V

L6-30P

10

3

30A

Full load runtime (minutes)

Half load runtime (minutes)

Expandable battery runtime

External battery pack compatibility

DC system voltage (VDC)

2 minutes (5400 watts)

8.5 minutes (2700 watts)

Runtime is expandable with external battery packs

BP192V12-3U;BP192V557C-1PH;BP192V787C-1PH;BP192V1037C-1PH;BP192V1407C-1PH

192

Page 3
Image 3
Tripp Lite SU6000RT4UHV Frequency compatibility, Output voltage regulation Battery mode, Output circuit breaker, Input