Tripp Lite TE600 Specifications, System Overview, Output, Input, Battery, Leds Alarms & Switches

Models: TE600

1 4
Download 4 pages 35.85 Kb
Page 2
Image 2
Specifications

Specifications

SYSTEM OVERVIEW

Voltage compatibility

120V AC

 

 

Frequency60Hz compatibility

OUTPUT

Output VA

Output watts

Output nominal voltage

Output voltage regulation

Output frequency regulation

Outlet quantity / type

INPUT

600

425

120V AC

LINE MODE: Sine wave line voltage 120V (-18% / +8%)

BATTERY MODE: PWM sine wave output 120V +/-5%

LINE MODE: Passes line frequency of 60Hz +/-10%

BATTERY MODE: Inverter output regulated to 60Hz +/-0.5Hz

6 NEMA 5-15R

Maximum input amps

Input connection type

Input cord length

Recommended Electrical Service

BATTERY

12A / 1440 watts

NEMA 5-15P, right-angle plug

6 ft., 14 gauge

15A 120V

Full load runtime

Half load runtime

DC system voltage

Typical battery lifespan

9 minutes (600VA)

22 minutes (300VA)

12 VDC

3-6 years, depending on usage

Battery recharge rate

2-4 hours to 90%

Replacement Battery

RBC52 (quantity 2)

Cartridge

 

 

 

VOLTAGE REGULATION

 

Voltage regulation

Automatic Voltage Regulation (AVR) circuits maintain clean, regulated computer-grade 120V nominal output, without

description

using battery power, during brownouts to 75V and overvoltages to 147V

 

 

Overvoltage

Input voltages between 128 and 147V AC are reduced by 12%

correction

 

 

 

Direct pass through

Input voltages between 108 and 127V AC are passed on to connected equipment unchanged

 

 

Brownout correction

Input voltages between 93 and 107V AC are boosted by 14%

 

 

Severe brownout

Input voltages between 75 and 92V AC are boosted by 30%

correction

 

 

 

LEDS ALARMS & SWITCHES

Front panel LEDs

Alarms

4 front panel LEDs indicate line power status, battery power status, battery low/replace status and voltage regulation operation

Audible alarm with 15 second delay sounds to indicate loss of utility power. Alarm can be silenced by pressing front panel alarm cancel button. Once silenced, alarm will re-sound when approximately 2 minutes runtime remain.

Switches

Includes 2 front panel switches — one main on/off power switch and one dual function "alarm cancel" / "self test" button

SURGE / NOISE SUPPRESSION

AC surge suppression 480 joules