Turbo Air TGM-11R, TGM-5R, TGM-22R Electronic Controller Instruction, Heater, Pre-cool, Max time

Models: TGM-22RV TGF-13F TGF-23F TGM-14RV TGF-49F TGM-33R TGM-35R TGM-45R TGM-69R TGM-14R TGM-11RV TGM-48R TGM-22R TGM-5R TGM-11R

1 128
Download 128 pages 61.87 Kb
Page 105
Image 105
Pre-cool

ELECTRONIC CONTROLLER INSTRUCTION

No

Control Function

Control Objects

 

 

Contents

Remark

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

Turbo

Compressor

6.

If you press the Turbo Freeze button during the defrost mode,

 

Freeze

Evap-Fan Motor

 

display panel displays Turbo Freeze mode but actually The Turbo

 

 

Con-Fan Motor

 

Freeze mode will start after defrost mode is completed.

 

 

 

LED

7.

If defrost mode occurs during the Turbo Freeze mode, the defrost

 

 

 

 

mode will start after the Turbo Freeze mode is completed

 

 

 

 

 

 

 

TEMPERATURE

 

 

 

 

 

Turbo air

 

 

LAMP

 

 

 

 

 

 

 

 

POWER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Long Beach, CA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T.F. FAN DOOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TURBO FREEZE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

Determination

 

1. Defrost mode is controlled by a time interval setting.

 

 

Of

 

2. The time interval setting can be set by shifting dip s/w on the PCB

 

Defrost

 

 

board.

 

 

 

 

 

 

 

 

 

 

 

 

3.The time interval setting is as follows. Dip Switch

NO.1

NO.2

Cycle time(hours)

0

0

12

1

0

10

0

1

8

1

1

6

4.Factory setting is to defrost every 8 hours ( see the above picture.)

5.The first defrost mode will start at half of time interval setting of when unit was plugged-in.

5

Defrost

Heater

1. Defrost step

 

 

 

 

Function

Compressor

 

 

 

 

 

Pre-cool

Heater

Pause

Fan Delay

 

 

Evap-Fan Motor

 

 

 

Con-Fan Motor Comp.

on

off

off

on

 

 

 

F-fan motor

on

off

off

off

 

 

 

C-fan motor

on

off

off

on

 

 

 

Heater

off

on

off

off

 

 

 

Max time

30 min.

40 min.

3 min.

5 min.

 

 

 

 

 

If D-sensor temperature

 

If D-sensor

 

 

 

 

 

is over 50˚F, heater

 

temp. lower

 

 

 

 

 

goes off.

 

than 14˚F,

 

 

 

 

 

If D-sensor is in error,

 

then F-fan

 

 

 

 

 

heater goes off

 

turns on

 

 

 

 

 

automatically 40 min

 

immediately

 

 

 

 

 

after activated.

 

 

A. Pre-Cool Step

a. It prevents from extreme temperature rise during defrost mode. b. Comp. Con-Fan Motor and Evap-Fan Motor run continuously

during pre-cool step.

c. 88 LED indicates inside temperature.

d. If F-sensor is sensing lower temperature than (-22)˚F(-30˚C) or pre-cool step interval reach in 30 minutes, pre-cool step goes off.

e. Turbo Freeze mode is only one time prior to pre-cool step. B. Heater defrost step

a. The defrost heater is energized. b. 88 LED displays 'dF'

c. The defrost heater warms the evaporator coil thereby melting all frost that accumulated during the previous refrigeration cycle.

e. When D-sensor is higher than 47˚F(8˚C… ), heater goes off.

102

Page 105
Image 105
Turbo Air TGM-5R, TGM-22R, TGM-48R, TGM-11RV, TGM-14R manual Electronic Controller Instruction, Heater, Pre-cool, Max time