Installation & Service Manual | NSSD |
Defrost Information
See
Defrost Control Chart
|
| Defrost |
|
Defrost | Defrosts | Duration | Term. |
Type | Per Day | (Min) | Temp. |
Off Time | 6 | 28 | |
Electric | 6 | 36 | 50°F |
Gas | 6 | 55°F |
E = Electric Defrost Termination G = Gas Defrost (Fan Delay)
F/S = Electric Defrost Failsafe (Opt.)
NOTE
The termination klixon for gas defrost is located at the bypass check valve at the left end of the evaporator coil.
Most klixons are located on the right end of the evaporator coil. The diagram shows the location for each defrost type that uses a klixon.
CAUTION
If electronic sensors are used in place of the klixons, the sensors must be located in the same location as the klixons for that defrost type. Any other locations will effect the refrigeration efficiency of the case.
WIRING DIAGRAMS
ELECTRICIAN NOTE - OVERCURRENT
PROTECTION
120V circuits should be protected by 15 or 20 Amp devices per the requirements noted on the cabinet nameplate or the National Electrical Code, Canadian Electrical Code - Part 1, Section 28. 208V defrost circuits employ No. 12 AWG field wire leads for field connections. On remote cases intended for end to end
The following wiring diagrams on pages 8 thru 11 will cover the NSSD case circuits including all defrost and lighting wiring circuits.
March, 2002 | Page 7 |