United States Stove 1557M, 1357M PART E - Figure, Does Not Pass Through A Combustible Wall

Models: 1357M 1557M

1 28
Download 28 pages 47.62 Kb
Page 12
Image 12
PART E - (Figure 12)

FIGURE 12, PART D

MINIMUM CHIMNEY CLEARANCES FROM MASONRY TO SHEET STEEL SUPPORTS AND COMBUSTIBLES 2 IN.

SHEET STEEL SUPPORTS

CHIMNEY SECTION

 

CHIMNEY THIMBLE

CHIMNEY

FLUE

CONNECTOR

 

2 IN.

CHIMNEY

AIR SPACE

 

MASONRY CHIMNEY CONSTRUCTED

TO NFPA 211

MINIMUM CLEARANCE 2 IN. ALL AROUND

1 IN. AIR SPACE TO CHIMNEY LENGTH

CHIMNEY CONNECTOR

TO HEATER

SOLID INSULATED, LISTED

FACTORY-BUILT CHIMNEY

LENGTH (12 IN. LONG MIN.)

SHEET STEEL SUPPORTS

(24 GAUGE MIN. THICKNESS)

4.Use an 8" inside diameter solid insulated listed factory-built chimney length which has 1" or more of solid insulation. The minimum length of this chimney section shall be 12" and will serve as a pass-through for the 6" diameter chimney connector. There must be at least a 12" air space between the outer wall of the chimney section and any combustible materials. The chimney section shall be concentric with and spaced 1" away from the chimney connector by means of sheet steel support plates on both ends of the chimney section. The opening in the combustible wall shall be covered and the chimney section supported on both sides with sheet steel supports which are at least 24 gauge (0.024") in thickness. The sheet steel supports shall be securely fastened to wall surfaces on all sides and shall be sized to fit and hold the chimney section. Fasteners used to secure chimney sections shall not penetrate chimney flue liner. See Part D.

5.A listed factory-built wall pass-through system may be purchased and installed according to the instructions packaged with it to provide a safe method of passing the chimney connector through a combustible wall for connection to a masonry chimney.

Additional requirements pertaining to Figure 8 and the above wall pass-through systems:

1.Insulation material used as part of wall pass-through system shall be of noncombustible material and shall have a thermal conduc- tivity of 1.0 Btu • in./ft.² • °F (4.88 kg • cal/hr • m² • °C) or less.

2.All clearances and thicknesses are minimums: larger clearances and thickness are acceptable.

3.A chimney thimble, as shown for 3" and 4" above (Parts C and D) shall be for types "3" and 4" connections to facilitate removal of the chimney connector for cleaning. The chimney thimble shall be of ASTM C315 fireclay with 5/8" minimum wall thickness, or material or equivalent durability. The inside diameter of the thimble shall be sized for the proper snug fit of a 6" diameter chimney connector pipe. The thimble shall be installed without damage to the chimney flue. The thimble shall extend through the chimney wall to, but not beyond, the inner surface of the chimney flue and shall be permanently cemented in place with high temperature cement.

4.A chimney connector to a masonry chimney, except for 2" above (Part B), shall extend through the wall pass-through system to the inner face of the chimney flue, but not beyond. It does not have to be fastened in place so long as it cannot accidently be pulled out of the chimney or shoved into the chimney flue. If fasteners are used to secure the chimney connector to a masonry chimney, the fasteners shall not penetrate the chimney flue liner.

5.Any material used to close up any opening for the connector shall be noncombustible.

PART E - (Figure 12)

In addition to the methods shown by A, B, C, and D of Figure 12, a listed factory-built wall pass-through system may be purchased and installed according to the instructions packaged with it to provide a safe method of passing chimney con- nector through a combustible wall for a connection to a masonry chimney.

CONNECTION OF CHIMNEY CONNECTOR TO A MASONRY CHIMNEY WHEN CHIMNEY CONNECTOR

DOES NOT PASS THROUGH A COMBUSTIBLE WALL

If the chimney connector does not have to pass through a combustible wall to get to a masonry chimney, simply connect the chimney connector directly to the masonry chimney's chimney thimble as described and shown by parts C and D of Figure 12. Remember, the chimney connector should extend into the chimney thimble to the innerface of the chimney flue but not beyond; if the chimney connector is extended through the chimney thimble into the chimney flue, resistance to the flow of smoke and gases up the chimney will occur; that flow resistance will have an adverse affect on the opera- tion and performance of the heater and venting system.

12

Page 12
Image 12
United States Stove 1557M, 1357M owner manual PART E - Figure, Does Not Pass Through A Combustible Wall