United States Stove 58242 owner manual Installation, Special Mobile Home Requirements

Models: 58242

1 20
Download 20 pages 60.3 Kb
Page 10
Image 10
SPECIAL MOBILE HOME REQUIREMENTS

Installation

OUTSIDE AIR SUPPLY (optional, unless installing in a mobile home)

Depending on your location and home construction, outside air may be necessary for optimal performance.

Metal pipe (solid or flexible) must be used for the outside air installation. PVC pipe is NOT approved and should NEVER be used.

A wind shield over the termination of the outside air pipe or a 90-degree elbow or bend away from the prevailing winds MUST be used when an outside air pipe is installed through the side of a building. The outside air termination MUST be at least 1-foot away from the exhaust system termination.

The outside air pipe on your Forester stove is 2” OD. The outside air connecting pipe must be at least 2” ID. The outside air connection used MUST NOT restrict the amount of air available to your stove. The outside air connecting pipe must be as short and free of bends as possible, and it must fit over, not inside, the outside air connection to the stove.

FIGURE 7

EXHAUST/INLET LOCATIONS

FIGURE 8

TYPICAL FRESH AIR TERMINATION

NOTE: Dimensions from the floor to your stoves inlet/exhaust pipes are approximate and may vary depending on your installation.

SPECIAL MOBILE HOME REQUIREMENTS

WARNING! - DO NOT INSTALL IN A SLEEPING ROOM

CAUTION! - THE STRUCTURAL INTEGRITY OF THE MOBILE HOME FLOOR, WALL, AND CEILING/ROOF MUST BE MAINTAINED.

In addition to the previously detailed installation requirements, mobile home installations must meet the following requirements:

The stove must be permanently attached to the floor.

The stove must be electrically grounded to the steel chassis of the mobile home with 8 GA copper wire using a serrated or star washer to penetrate paint or protective coating to ensure grounding.

Vent must be 3 or 4-inch “PL” Vent and must extend a minimum or 36-inches above the roofline of the mobile home and must be installed using a UL listed ceiling fire stop and rain cap.

When moving your mobile home, all exterior venting must be removed while the mobile home is being relocated. After relocation, all venting must be reinstalled and securely fastened.

Outside Air is mandatory for mobile home installation. See your dealer for purchasing.

Check with your local building officials as other codes may apply.

10

USSC

Page 10
Image 10
United States Stove 58242 Installation, Special Mobile Home Requirements, Warning! - Do Not Install In A Sleeping Room