INSTALLATION

Thefollowingformulacanbeusedtodeterminethemaximum heater ratingperthedefinition of unconfinedspace:

BTU/HR = (L1+L2) Ft x (W) Ft x (H) Ft x 1000

50

Considertwoconnectingroomswithanopenareabetween,

 

 

with the following dimensions:(See Fig. 2, Example)

 

 

L1=15-1/2 Ft., L2=12 Ft., W=12 ft., H=8Ft

 

H (8')

50

 

L2 (12')

 

=52800 BTU/HR

 

 

 

 

L1 (15-1/2')

W (12')

 

 

If there were a door between the two rooms the calculation

 

 

would be based only on the room with the heater. BTU/HR=(15-1/2) x (12) x (8) x 1000

50

FIGURE 2.

=29760 BTU/HR

WARNING WARNING WARNING

When installing the appliance directly on carpeting,tile or other combustible material,otherthanwoodflooring,theappliancemustbeinstalledonametalor woodpanelextendingthefullwidthanddepthoftheappliance.

Iftheareainwhichtheheatermaybeoperatedissmallerthanthatdefinedasan unconfined space or if the building is of unusually tight construction,provide adequatecombustionandventilationairbyoneofthemethodsdescribedinthe NationalFuelGasCode,ANSIZ223.1,Section5.3,orapplicablelocalcodes.

Ensure the minimum clearances shown in FIGURE 3 are maintained for accessibility for purposes of servicing and proper operation.Left and right clearancesaredeterminedwhenfacingthefrontoftheheater.

36"

8"

8"

42"

4"

Maintaintheseclearancesto ensure adequate space around air opening for properoperation.

Minimumclearancestocombustibles:

Topofheater

36"

Sidesofheater

8"

Frontofheater

42"

Rearofheater

4"

FIGURE 3. Minimum Clearances

7

Page 7
Image 7