Utica Gas-fired Boiler manual Connecting Gas Service, Do Not Use An Open Flame

Models: Gas-fired Boiler

1 28
Download 28 pages 13.85 Kb
Page 13
Image 13
CONNECTING GAS SERVICE

CONNECTING GAS SERVICE

1.Connect gas service from meter to control assembly in accordance with ANSI Z223.1 and local codes or utility. A ground joint union should be installed for easy removal of gas control for servicing. A drip leg or trap must be installed at the bottom of a vertical section of piping at the inlet to the boiler. A pipe compound resistant to the action of liquified petroleum gases must be used on all threaded pipe connections. Check with the local utility for location of manual shutoff valve if required. See figure 13 below.

2.The gas line should be of adequate size to prevent undue pressure drop and never smaller than the pipe size of the main gas control valve. See chart below.

3.To check for leaks in gas piping, use a soap and water solution or other approved method.

DO NOT USE AN OPEN FLAME. WARNING:

DO NOT USE AN OPEN FLAME.

4.Disconnect the boiler from the gas supply piping system during any pressure testing of the gas piping. After reconnecting, leak test the gas connection and boiler piping before placing the boiler back into operation.

Maximum Capacity of Pipe in

Cubic Feet of Gas Per Hour

(Gas pressure = 0.5 psig or less, pressure drop =

.5 in.w/c)

Nominal

 

Length of Pipe (Feet)

 

Iron Pipe

 

 

 

 

 

 

 

Size

10'

20'

30'

40'

60'

80'

100'

1/2"

175

120

97

82

66

57

50

3/4"

360

250

200

170

138

118

103

1"

680

465

375

320

260

220

195

1.1/4"

1400

950

770

660

530

460

400

 

 

 

 

 

 

 

 

For additional information refer to “Table C” of the National Fuel Gas Code Handbook.

FIGURE 13

PAGE 12

Page 13
Image 13
Utica Gas-fired Boiler manual Connecting Gas Service, Do Not Use An Open Flame