Utica Gas-fired Boiler manual Ratings And Data, Natural Gas And Propane Gas, Explanatory Notes

Models: Gas-fired Boiler

1 28
Download 28 pages 13.85 Kb
Page 27
Image 27
RATINGS AND DATA

 

 

 

RATINGS AND DATA

 

 

 

 

NATURAL GAS AND PROPANE GAS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

§

§

§ **

 

 

Natural

Propane

 

Boiler

A.G.A.

Heating

I=B=R

NetRating

No.

Recommended

Gas

Orifice

Water

No.

Input

Capacity

NetOutput

Sq. Ft. HW

of

Air Cushion

Orifice

Drill

Content

 

Btu/Hr.

Btu/Hr.

Btu/Hr

@ 170

o

Burners

Tank

Drill Size

Size

(Gals.)

 

 

MGB 50

50,000

42,000

37,000

243

 

1

15

30

47

2.4

MGB 75

75,000

63,000

55,000

365

 

2

15

33

50

4.0

MGB 100

100,000

83,000

72,000

481

 

2

30

30

47

4.0

MGB 125

125,000

104,000

90,000

603

 

3

30

31

49

5.6

MGB 150

150,000

124,000

108,000

719

 

3

30

30

47

5.6

MGB 175

175,000

143,000

124,000

829

 

4

30

31

49

7.2

MGB 200

200,000

165,000

143,000

957

 

4

30

30

47

7.2

MGB 250

250,000

205,000

178,000

1189

 

5

30

30

47

8.8

 

 

 

 

 

 

 

 

 

 

 

MGB 300

299,999

243,000

214,000

1368

 

6

60

30

47

10.4

STANDARD EQUIPMENT: Boiler Jacket, Cast Iron Boiler Battery, Combination Aquastat Relay, Theraltimeter Gauge,Circulator with return piping to boiler, Main Gas Burners, Combination 24 Volt Gas Control (includes automatic gas valve, gas pressure regulator, automatic pilot, safety shutoff, pilot flow adjustment, pilotfilter), A.S.M.E. Relief Valve, Drain Cock, Spill Switch, Rollout Switch, Automatic Vent damper. Not shown are a wiring harness, thermocouple, and non-linting safety pilot.

OPTIONAL EQUIPMENT: Intermittent Electric Ignition Pilot System.

EXPLANATORY NOTES

--All boilers are design certified for installation on noncombustible floor. --For installation on combustible floors use combustible floor kit.

--Recommended chimney height 20 feet. In special cases where conditions permit, chimney height may be reduced to 10 feet. Refer to the latest revision of NFGC part 11.

--Electric service to be 120 Volts, 15 Amps, 60 Hz.

--The MEA number for the MGB series boiler is 19-79 Vol. II

§For elevations above 2000 feet, ratings should be reduced at a rate of 4% for each 1000 feet above sea level.

Tank sized for non-ferrous baseboard or radiant panel systems. Increase size for cast iron baseboard and radiation.

Base on 170' temperature in radiators.

--Net I=B=R ratings include 15% allowance for normal piping and pick-up load. Manufacturer should be consulted on installations having otherthan normal piping and pick-up requirements.

**For equivalent square feet of radiation, divide I=B=R output by 150.