CHECK SAFETY CONTROL CIRCUIT, after burner adjustments are made, for satisfactory operation.

1.Pilot: With main burner operating, turn the pilot gas adjusting screw clockwiseROLLOUT & SPILL SWITCH until pilot gas is turned off. See figures 14, 15, & 16 on pages 14 & 15. Within 90 seconds

the main gas control should close, shutting off the gas to the main burner.

2.High limit control (figure 22 on page 19). Remove cover and note temperature setting. Decrease this setting to minimum and operate boiler. When the boiler water temperature exceeds the control temperature setting, the control will open the circuit, closing the automatic main gas valve.

MGB SERIES REPLACEMENT PARTS

ROLLOUT & SPILL SWITCH

ITEM

PART

 

 

NO.

NO.

DESCRIPTION

OTY.

 

 

 

 

1

3262001

TEMP. SENSOR BRACKET

1

2

AQ02101

CONTROL-FIXED TEMPERATURE

1

 

 

THERMO (ROLLOUT SWITCH)

 

3

HW06501

SCREW - #6 X1/4 HEX HD

2

THE ROLLOUT SWITCH IS LOCATED ON THE BASE AND FLUE COLLECTOR

NOTE: THE QUANTITIES ABOVE ARE FOR EACH SWITCH.