Pressure Testing Gas Supply Piping System

OWNER’S MANUAL

INSTALLATION

Continued

CHECKING GAS

CONNECTIONS

Pressure Testing Heater Gas Connections WARNING: Test all gas pip- ing and connections for leaks after installing or servicing. Cor- rect all leaks at once.

Manual background WARNING: Never use an open flame to check for a leak. Apply a mixture of liquid soap and water to all joints. Bubbles forming show a leak. Correct all leaks at once.

Manual background CAUTION: Make sure exter- nal regulator has been installed between propane/LP supply and heater. See guidelines under Con- necting to Gas Supply, page 12.

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1.Disconnect appliance with its appliance main gas valve (control valve) and equip- ment shutoff valve from gas supply pip- ing system. Pressures in excess of 1/2 psig will damage heater regulator.

2.Cap off open end of gas pipe where equipment shutoff valve was connected.

3.Pressurize supply piping system by ei- ther using compressed air or opening propane/LP supply tank valve.

4.Check all joints of gas supply piping system. Apply mixture of liquid soap and water to gas joints. Bubbles form- ing show a leak.

5.Correct all leaks at once.

6.Reconnect fireplace and equipment shutoff valve to gas supply. Check re- connected fittings for leaks.

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1.Close equipment shutoff valve (see Fig- ure 22).

2.Pressurize supply piping system by ei- ther using compressed air or opening propane/LP supply tank valve.

3.Check all joints from propane/LP sup- ply tank to equipment shutoff valve (see Figure 23). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.

4.Correct all leaks at once.

Equipment

ShutoffOpen

Valve

Closed

Figure 22 - Equipment Shutoff Valve

Propane/LP

Supply Tank

Figure 23 - Checking Gas Joints

Pressure Testing Heater Gas Connections

1.Open equipment shutoff valve (see Fig- ure 22).

2.Open propane/LP supply tank valve.

3.Make sure control knob of heater is in the OFF position.

4.Check all joints from equipment shutoff valve to thermostat gas valve (see Fig- ure 23). Apply mixture of liquid soap and water to gas joints. Bubbles form- ing show a leak.

5.Correct all leaks at once.

6.Light heater (see Operating Heater, pages 14 and 15). Check all other in- ternal joints for leaks.

7.Turn off heater (see To Turn Off Gas to Appliance, page 14).

8.Replace front panel.

Thermostat Gas

Valve Location

Equipment

Shutoff

Valve

104432

13