Motorola BT100 operation manual Testing Return Gain and Response

Models: BT100

1 52
Download 52 pages 62.92 Kb
Page 42
Image 42

Bench Testing

4-3

1Perform steps 1 through 6 in Measuring Forward Gain above.

2Estimate the ambient temperature and find the required gain reserve by referring to Table 3-3. Reduce the gain at the highest frequency by the amount given in the table.

Example:

The ambient temperature is 70°F. The table indicates that the required gain reserve is 4 dB. Reduce the gain by 4 dB.

The operational gain is the sum of the measured gain after performing Step 2, plus all losses, such as power combiner, cable loss, equalizer, and cable simulator.

The sweep response is essentially flat at this point. If the response exhibits tilt, the cable equalizer must be changed. Install a higher equalizer value if the gain is greater at the low frequencies; install the next lower equalizer value if the gain is less at the low-end frequencies.

3Measure the gain excursions from an average value within the bandpass.

The result is the peak-to-valley flatness. Some improvement is possible by adjusting the flatness controls on the BDR board as described in Section 3, “Amplifier Setup,” Flatness Control. Figure 3-4 illustrates the location of these controls on the BDR.

Testing Return Gain and Response

After configuring the return path, you can test the return bandpass to ensure compliance with specifications. When testing the return path, remember that it is a flat response. Therefore, the cable simulator must remain in the test set-up and must remain set to the same cable equivalent as in the forward sweep test. This provides an approximate indication of the frequency response, which you can achieve in the field.

To test for return gain and response:

1Reconnect the test equipment and switch the sweep input and sweep output leads of the BT100 under test to be opposite of the connection shown in Figure 4-1.

2Remove the 20 A fuse (F1) at the input port and replace the 20 A fuse (F2, F3, F4, or F5) at the output port (Figure 2-9) before you apply power.

3Re-adjust the test equipment to sweep from 4 MHz through the maximum return band frequency plus 10 MHz (Example – 50 MHz for S-split).

The expected response is flat. Any tilt, which is due to the return equalizer, must average out to a flat response in a cascade of amplifiers. A slope adjustment is not available in the return bandpass.

4Measure the gain at the maximum return band frequency (example 40 MHz for S-split).

The amplifier gain is the sum of: the measured gain, the insertion loss of the return cable equalizer at the maximum return band frequency, the insertion loss of the power combiner, any pads installed in either the input or output pad locations, plus the cable simulator loss at the maximum return band frequency. The amplifier gain must meet advertised specifications for the return path.

BT100 Installation and Operation Manual

Page 42
Image 42
Motorola BT100 operation manual Testing Return Gain and Response