Minimum Non-combustible Material Clearances

VANGUARD FLAME-MAX®

UNVENTED PROPANE/LP GAS LOG HEATER

INSTALLATION

Continued

Minimum Non-combustible Material Clearances

If Not Using Mantel

You must have non-combustible material(s) above the fireplace opening. Non-combus- tible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch thick. With sheet metal, you must have non-combus- tible material behind it. Non-combustible material must extend at least 8" up (for all models). If non-combustible material is less than 12", you must install the fireplace hood accessory (24", 30", and 36” models only). See Figure 4 on page 7 and Figure 5 for minimum clearances.

IMPORTANT: If you cannot meet these minimum clearances, you must operate heater with chimney flue damper open. Go to Installing Damper Clamp Accessory for Vented Operation, page 10.

If Using Mantel

You must have non-combustible material(s) above the fireplace opening. Non-combus- tible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch thick. With sheet metal, you must have non-combus- tible material behind it. Non-combustible material must extend at least 8 inches up (for all models). If non-combustible material is less than 12", you must install the fireplace hood accessory (24", 30”, and 36" models only). Even if non-combustible material is more than 12", you may need the hood accessory to deflect heat away from your mantel shelf. See Figure 5 and Figures 6 and 7, page 9, for minimum clearances.

IMPORTANT: If you cannot meet these minimum clearances, you must operate heater with chimney flue damper open. Go to Installing Damper Clamp Accessory for Vented Operation, page 10.

Non-Combustible

Requirements for

Material Distance (A)

Safe Installation

 

 

12" or more

Non-combustible material OK.

Between 8" and 12"

24", 30", or 36” Models: Install fireplace hood accessory

 

(GA6050, GA6052, or GA6053 see Accessories, page 30).

 

18" Model: Non-combustible material OK.

Less than 8"

Non-combustible material must be extended to at least 8".

 

See Between 8" and 12", above. If you cannot extend

 

material, you must operate heater with flue damper

 

open.

 

 

Heat Resistant Heat Resistant

Material

(A)

Figure 5 - Heat Resistant Material (Slate,

Marble, Tile, etc.) Above Fireplace

8