Vermont Casting BHDT36 installation instructions Vertical Thru The Roof Installation, Storm Collar

Models: BHDT36

1 34
Download 34 pages 38.12 Kb
Page 23
Image 23
SHEETMETAL  SCREWS (#5) Ñ

VERTICAL THRU THE ROOF INSTALLATION

1.Locate your fireplace.

2.Plumb to centre of the (4") collar from ceiling above and mark position.

3.Cut opening equal to 9-3/8" x 9-3/8" (240 mm x 240 mm).

4.Proceed to plumb for additional openings through the roof. In all cases, the opening must provide a minimum of 1 inch clearance to the vent pipe, i.e., the hole must be a minimum of 9-3/8" x 9-3/8" (240 mm x 240 mm).

5.Place firestop(s) 7DVFS into position and secure. (Fig. 54)

6.Install roof support (Fig. 52) and roof flashing making sure upper flange of flashing is below the shingles. (Fig. 55)

7.Install appropriate pipe sections until above the flash- ing. (See Fig. 53 for #'s 7, 8 and 9).

8.Install storm collar and seal around the pipe.

9.Add additional vent lengths for proper height.

10.Apply high temperature sealant to 4" and 7" collars of vent termination and install.

Attic

 

 

Insulation

 

 

Shield

11"

 

 

 

JOIST

Ceiling

11"

UPPER FLOOR

Installation

 

 

 

 

 

JOIST

 STORM COLLAR FIRESTOP

SPACER

NAILS (4)

Fig. 54

Fig. 54 If there is a room above ceiling level, firestop spacer must be installed on both the bottom and the top side of the ceiling joists. If an attic is above ceiling level a 7DVAIS (Attic Insulation Shield) must be installed.

Fig. 55. The enlarged ends of the vent section always face downward.

SHEETMETAL Manual background SCREWS (#5) Ñ

3 PER JOINT

Manual background SEALANT

Manual backgroundManual background STORM COLLAR

Fig. 55

- 23 -

Page 23
Image 23
Vermont Casting BHDT36 Vertical Thru The Roof Installation, Storm Collar, SHEETMETAL SCREWS #5 Ñ 3 PER JOINT SEALANT