HOW TO USE THE VENT GRAPH

1.Determine the height of the centre of the horizontal vent pipe exiting through the outer wall. Using this dimension on the Sidewall Vent Graph (Fig. 39), locate the point it intersects with the slanted graph line.

2.From the point of this intersection, draw a vertical line to the bottom of the graph.

3.Select the indicated dimension, and position the fireplace in accordance with same.

EXAMPLE A:

If the vertical dimension from the floor of the unit is 11 feet (3352mm) the horizontal run to the face of the outer wall must not exceed 14 feet (4267mm).

EXAMPLE B:

If the vertical dimension from the floor of the unit is 7 feet (2133mm), the horizontal run to the face of the outer wall must not exceed 8-1/2 feet (2590mm).

VERTICAL SIDEWALL VENTING GRAPH

(Dimensions in Feet)

30

 

 

 

29

 

 

 

28

 

TOTHE

VERTICAL

27

 

 

 

 

26

 

 

 

25

 

CENTREOF

DIMENSION

24

 

 

 

 

23

 

 

 

22

 

 

 

21

 

 

 

20

 

THEHORIZONTAL

FROMTHEFLOOR

19

 

18

 

17

 

 

 

 

16

 

 

 

15

 

 

 

14

 

 

 

13

 

VENTPIPE

OFTHEUNIT

 

 

12

eg: A

 

 

11

 

 

 

 

 

 

10

 

 

 

9

 

 

 

8

 

7

 

eg: B

6

 

 

5

 

4

 

3

 

34 5￿ 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Fig. 39

SEE PAGE 21 FOR VENTING

REQUIREMENTS FOR SNORKELS.

- 19 -

VERTICAL SIDEWALL INSTALLATION

STEP 1

Locate vent opening on the wall. It may be necessary to first position the fireplace and measure to obtain hole location. Depending on whether the wall is combustible or non- combustible, cut opening to size.

(For combustible walls first frame in opening).

VERTICAL SIDEWALL APPLICATION

Vent Opening Ñ

Combustible Wall Fig. 40

(240mm)

Manual backgroundManual background9-3/8"Manual backgroundManual background

9-3/8" (240mm)

(framing detail)

Vent Opening Ñ

Noncombustible Wall Fig. 41

7-1/2" Manual background (190mm)

COMBUSTIBLE WALLS (Fig. 40): Cut a 9-3/8"H x 9-3/8"W (240 mm x 240 mm) hole through the exterior wall and frame as shown

NON-COMBUSTIBLE WALLS (Fig. 41): Hole opening must be

7.5" (190 mm) in diameter.

STEP 2

Fiig. 42. Measure wall thickness and cut adjustable zero clearance sleeve parts to proper length (MAXIMUM 12"/ 305mm). Adjust sleeve to minimum (9-3/8" x 9-3/8") and attach to firestop with #8 sheet metal screws (supplied). Install firestop assembly.

Zero clearance sleeve is only required for combustible walls.