TROUBLE SHOOTING THE GAS CONTROL SYSTEM
SIT NOVA 820 MILLIVOLT VALVE
Note: Before trouble shooting the gas control system, be sure external gas shut off is in the "On" position.
WARNING: BEFORE DOING ANY GAS CONTROL SERVICE WORK, REMOVE GLASS FRONT.
SYMPTOM | POSSIBLE CAUSES | CORRECTIVE ACTION | |
|
|
|
|
1. Spark ignitor will not light | A. Defective or misaligned | Using a match, light pilot. If pilot lights, turn off pilot and | |
|
| electrode at pilot. | push the red button again. If pilot will not light - check gap |
|
|
| at electrode and |
|
|
|
|
|
| B. Defective ignitor (Push Button) | Push Piezo Ignitor Button. Check for spark at electrode and |
|
|
| pilot. If no spark to pilot, and electrode wire is properly |
|
|
| connected, replace ignitor. |
|
|
|
|
2. Pilot will not stay lit after | A. Defective pilot generator | 1. Check pilot flame. Must impinge on thermocouple/ | |
carefully following lighting | (thermocouple), remote wall | thermopile. Note: this pilot burner assembly utilizes both | |
instructions. | switch. | a thermocouple and a thermopile. The thermocouple | |
|
|
| operates the main valve operation (On and Off). Clean |
|
|
| and or adjust pilot for maximum flame impingement on |
|
|
| thermopile and thermocouple. |
|
|
|
|
|
| B. Defective automatic valve | Turn valve knob to "Pilot". Maintain flow to pilot; millivolt |
|
| operator. | meter should read greater than 10 mV. If the reading is |
|
|
| okay and the pilot does not stay on, replace the gas |
|
|
| valve. Note: An interrupter block (not supplied) must be |
|
|
| used to conduct this test. |
|
|
|
|
3. Pilot burning, no gas to | A. Wall switch or wires | Check wall switch and wires for proper connections. Jumper | |
burner, Valve knob "ON", | defective. | wire across terminals at wall switch, if burner comes on, | |
Wall Switch "ON". |
| replace defective wall switch. If okay, jumper wires across | |
|
|
| wall switch wires at valve, if burner comes on, wires are |
|
|
| faulty or connections are bad. |
|
|
|
|
|
| B. Thermopile may not be | 1. Be sure wire connections from thermopile at gas valve |
|
| generating sufficient | terminals are tight and thermopile is fully inserted into pilot |
|
| millivoltage. | bracket. |
|
|
| 2. One of the wall switch wires may be grounded. Remove |
|
|
| wall switch wires from valve terminals if pilot now stays lit, |
|
|
| trace wall switch wiring for ground. May be grounded to |
|
|
| fireplace or gas supply. |
|
|
| 3. Check thermopile with millivolt meter. Take reading at |
|
|
| thermopile terminals of gas valve. Should read |
|
|
| millivolts (minimum 150) while holding valve knob de- |
|
|
| pressed in pilot position and wall switch "Off". Replace |
|
|
| faulty thermopile if reading is below specified minimum. |
|
|
|
|
|
| C. Plugged burner orifice. | Check burner orifices for debris and remove. |
|
|
|
|
|
| D. Defective automatic valve | Turn valve knob to "On", place wall switch to "On" millivolt |
|
| operator. | meter should read greater than 100 mV. If the reading is |
|
|
| okay and the burner does not come on, replace the gas |
|
|
| valve. |
|
|
|
|
4. Frequent pilot flare outage | A. Pilot flame may be too low | Clean and/or adjust pilot flame for maximum flame | |
problem. | or blowing (high) causing the | impingement on thermopile and thermocouple. | |
|
| pilot safety to drop out. |
|
|
|
|
|
|
| B. Vent safety shutdown. | Check the vent system for blockage. Check all connections |
|
|
| on vent safety switch. |
|
|
|
|
- 14 -