Verona VECTIM304 Wirebranch circuit, Installation Manual, Danger, English, Recommended Minimum

Models: VECTIM365 VECTIM304

1 28
Download 28 pages 1.8 Kb
Page 10
Image 10
Recommended Minimum

 

 

 

 

Installation Manual

 

 

 

 

ENGLISH

 

Recommended Minimum

 

 

 

 

Wire size

 

 

 

(AWG)

 

 

0-4.8

20

12

 

 

4.9-6.9

30

10

 

 

7.0-9.9

40

8

 

 

10.0-11.9

50

8

 

 

12.0-14.9

60

6

 

 

Be sure your appliance is properly installed and

 

 

grounded by a qualified technician. Ask your

 

 

dealer to recommend a qualified technician or an

 

 

authorized repair service. This cooktop does not

 

 

require a neutral connection. If the cooktop Is to

 

 

be completely enclosed In a cabinet, feed the

 

 

cooktop cable through the opening in the cabinet.

 

 

Make the electrical connection following the

 

 

 

appropriate steps for your installation.

 

 

 

This appliance is manufactured with a green ground

 

 

wire connected to the cooktop chassis. After making

Figure 1�.

sure that the power has been turned off, connect the

 

 

flexible conduit from the cooktop to the junction box

4-Wire branch circuit

using a U.L. listed conduit connector. Figures 13 and

 

 

14 and the instructions provided below present the

Refer to figure 14:

most common way of connecting the cooktops. Your

1. Connect the green ground wire from the cooktop

local codes and ordinances, of course, take

 

 

to the ground wire in the junction box (bare or

precedence over these instructions. Complete

 

 

green colored wire).

electrical connections according to local codes and

2. Connect the red and black leads from the cooktop

ordinances

 

 

 

 

 

to the corresponding leads in the junction box.

 

 

 

 

 

DANGER

 

3. Connect the white wire from the cooktop to the

 

 

 

neutral (gray or white) wire in the junction box.

Risk of Electric Shock, frame grounded to

 

4.

Terminate and insulate the neutral (gray or white

 

 

colored wire) in the junction box.

neutral of appliance through a link.

 

 

 

 

 

Grounding through the neutral conductor is prohibited for new branch-circuit installations (1996 NEC); mobile homes; and recreational vehicles, or in an area where local codes prohibit grounding through the neutral conductor.

3-Wire branch circuit

Where local codes allow the connection of ground wire from the cooktop to the branch circuit neutral wire (gray or white colored wire) proceed as follows (see figure 13).

1. If local codes permit, connect the green GROUND wire from the cooktop to the branch circuit neutral wire (gray or white colored wire).

2. Connect the red and black leads from the cooktop to the corresponding leads in the junction box.

Figure 1�.

10

Page 10
Image 10
Verona VECTIM304, VECTIM365 manual Wirebranch circuit, Installation Manual, Danger, English, Recommended Minimum