Installation Manual
ENGLISH
Electrical Connections
DANGER
Disconnect power before servicing the product. Failure to do so could result in death or electrical shock.
General information
The flexible conduit (supplied) 3 feet long (100 cm) located at the right rear of the cooktop bottom box should be connected directly to junction box. Do not cut the conduit. A U.L - or CSA - listed conduit connector must be provided at each end of the power supply cable (at the cooktop and at the junction box.) A time delay fuse or circuit breaker is recommended. Do not ground to a gas pipe. Do not have a fuse in the grounding or neutral circuit.
Fuse both supply (phase) lines.
WARNING
The models may be powered at 240V or 208V.This cooktop does not require a neutral connection. If the cooktop is to be completely enclosed in a cabinet, feed the cooktop cable through the opening in the cabinet. Make the electrical connection following the appropriate steps for your installation.
Your cooktop must be connected to the proper electrical voltage and frequency as specified in the table on the right.
Figure 12. Location of serial tagConnect with copper wire onlyIf the house has aluminum wiring, follow the procedure below:
1.Connect the aluminum wiring to the copper wire by using special connectors designed and Underwriters
2.Aluminum/copper connection must conform with local codes and industry- accepted wiring practices.
WARNING
Improper connection of aluminum house wiring to the copper leads can result in a serious problem.
|
|
| Power Supply |
|
| |
| Model | 240 V 60 Hz | 208 V 60 Hz | Approval | ||
|
| code | ||||
|
|
|
|
|
| |
30” | VECTIM304 | 7,2kW | 30A | 6,2kW | 29,8A | 812T40IP |
36” | VECTIM365 | 10,8kW | 45A | 9,7kW | 46.6A | 812V50IQ |
A
WARNING
This touch control works using optical light sensing technology. When first connecting electrically or after a power failure, any direct strong light over the sensor area may affect the touch control functionality. When powering on the unit make sure that no strong light is shining direct over the touch control zone, it can compromise the
9