Cable Grounding and Termination
To maintain data transmission performance, network cabling must be terminated correctly. Termination requirements vary depending on the type of cable used for network connections – shielded or unshielded twisted pair - and the type of transceiver used.
Cable Grounding
The majority of LonWorks networks use
Shielded Twisted Pair
SHIELD GROUNDING CIRCUIT
470KW, 5%, ¼W
100nF, 100V, 10% Metallized Polyester
Figure 1. Cable Shield Grounding Circuit.
The 470KW resistor safely bleeds off any static charge on the cable’s shield, and the capacitor helps avoid DC and 50/60Hz ground paths from being formed through the shield. The cable shield should be grounded at least once per segment, and at each node if possible.
Cable Wiring and Termination
Termination of the network depends upon the type of transceiver used. In some installations, the termination circuit included on the
Option 1 – RS-485
The