Operation Mode – register 10 with choice of Auto or Manual as read only Input Error – register 4 with choice of Sensor Error or Ok as read only Process Value Input 1 – register 1 as read only
Process Value Input 2 – register 2 as read only Auto Set Point – register 7 as read/write
Alarm Status Output 2/3 – register 3 with choice of Ok, Alarm High, Alarm Low or Alarm Error as read only
Alarm Acknowledge – register 3 with choice to clear alarm as write only
Note: Selecting Manual control using the Operation Mode, an input error or inputting Set Point values less than
Operation Mode – register 301 with choice of Auto or Manual as read only Input Error – register 209 with choice of Sensor Error or Ok as read only Process Value Input 1 – register 100 as read only
Process Value Input 2 – register 104 as read only Auto Set Point 1 – register 300 as read/write Auto Set Point 2 – register 319 as read/write
Alarm Status Output 3 – register 110 with choice of Ok, Alarm High, Alarm Low, or Alarm Error as read only
Alarm Acknowledge – register 110 with choice to clear alarm as write only
Note: Selecting Manual control using the Operation Mode, an input error or inputting Set Point values less than
Operation Mode – register 200 with choice of Auto or Manual as read only Input 1 Error – register 101 with choice of Sensor Error or Ok as read only Input 2 Error – register 105 with choice of Sensor Error or Ok as read only Input 3 Error – register 109 with choice of Sensor Error or Ok as read only Process Value Input 1 – register 100 as read only
Process Value Input 2 – register 104 as read only Process Value Input 3 – register 108 as read only Auto Set Point 1 – register 300 as read/write Auto Set Point 2 – register 319 as read/write
Alarm Status Output 2 – register 102 with choice of Ok, Alarm High, Alarm Low, Alarm High Latched, Alarm Low Latched, Alarm High Silenced, Alarm Low Silenced, Alarm High Latched Silenced, Alarm Low Latched Silenced, Waiting for in Range Alarm, Alarm Disabled, or Alarm Error as read only
Alarm Status Output 3 – register 106 with choice of Ok, Alarm High, Alarm Low, Alarm High Latched, Alarm Low Latched, Alarm High Silenced, Alarm Low Silenced, Alarm High Latched Silenced, Alarm Low Latched Silenced, Waiting for in Range Alarm, Alarm Disabled, or Alarm Error as read only
Alarm 1 Acknowledge – register 312 with choice to clear alarm as write only Alarm 2 Acknowledge – register 331 with choice to clear alarm as write only
Note: Alarms configured are displayed. Alarms can not be acknowledged when the alarm condition still exists.