CLS200 Series (Loop 1 to 16 if available)
Operation Mode – register 264 to 279 with choice of Auto or Manual as read only
Input Error – registers 660 to 675 with choice of Ok, TC Reversed, TC Short, TC Open, RTD Open, or RTD Short as read only
Process Value – registers 363 to 378 as read only Auto Set Point – registers 330 to 345 as read/write
Alarm Status – registers 660 to 675 with choice of Ok, Low Deviation, High Deviation, Low Process, or High Process as read only
Alarm Acknowledge – registers 8311 to 8326 with choice to clear alarm as write only
Note: Alarms configured are displayed. Alarms can not be acknowledged when the alarm condition still exists.
Note: The Communication Specifications manual list absolute registers, which are the relative register with 40001 added to them. As an example, relative register 264 is absolute register 40265.
Series SD –Operation Mode – register 25 with choice of Auto or Manual as read only Input Error – registers 24 with choice of Ok or Error as read only Process Value – registers 20, 21 as read only
Auto Set Point – registers 27, 28 as read/write
Alarm 1 Status – registers 29 and 30 of Alarm 1 Ok, Alarm 1 Low Alarm, or Alarm 1 High Alarm as read only
Alarm 2 Status – always OK as this is the same output as communications.
Alarm 3 Status – registers 33 and 34 of Alarm 3 Ok, Alarm 3 Low Alarm, or Alarm 3 High Alarm as read only
Note: Alarms configured are displayed. Alarms can not be acknowledged when the alarm condition still exists.
In addition, the Series SD has many other parameters to read or change by clicking on the link SeriesSD. Be sure to submit any changes made on these screens using the Submit button at the bottom of the screen.
The following are screen captures from the Series SD:
20