Series F4P

Operation Mode – register 200 with choice of Auto or Manual as read only Input 1 Error – register 101 with choice of Sensor Error or Ok as read only Input 2 Error – register 105 with choice of Sensor Error or Ok as read only Input 3 Error – register 109 with choice of Sensor Error or Ok as read only Process Value Input 1 – register 100 as read only

Process Value Input 2 – register 104 as read only Process Value Input 3 – register 108 as read only Auto Set Point – register 300 as read/write

Alarm Status Output 2 – register 102 with choice of Ok, Alarm High, Alarm Low, Alarm High Latched, Alarm Low Latched, Alarm High Silenced, Alarm Low Silenced, Alarm High Latched Silenced, Alarm Low Latched Silenced, Waiting for in Range Alarm, Alarm Disabled, or Alarm Error as read only

Alarm Status Output 3 – register 106 with choice of Ok, Alarm High, Alarm Low, Alarm High Latched, Alarm Low Latched, Alarm High Silenced, Alarm Low Silenced, Alarm High Latched Silenced, Alarm Low Latched Silenced, Waiting for in Range Alarm, Alarm Disabled, or Alarm Error as read only

Alarm 1 Acknowledge – register 312 with choice to clear alarm as write only Alarm 2 Acknowledge – register 331 with choice to clear alarm as write only

Note: Alarms configured are displayed. Alarms can not be acknowledged when the alarm condition still exists.

MicroDIN

Operation Mode – register 200 with choice of Auto or Manual as read only Input Error – register 101 with choice of Sensor Error or Ok as read only Process Value Input 1 – register 100 as read only

Auto Set Point – register 300 as read/write

Alarm Status Output 2 – register 106 with choice of Ok, Alarm High, Alarm Low, Alarm High Latched, Alarm Low Latched, Alarm High Silenced, Alarm Low Silenced, Alarm High Latched Silenced, Alarm Low Latched Silenced, Waiting for in Range Alarm, Alarm Disabled, or Alarm Error as read only

Alarm Acknowledge – register 331 with choice to clear alarm as write only

Note: Alarms configured are displayed. Alarms can not be acknowledged when the alarm condition still exists.

Power Series

Heat Sink Temperature in Degrees C - register 1590 as read only

Load Current in Amps RMS on Line 1 - register 154 as read only (Based on configuration) Load Current in Amps RMS on Line 2 - register 164 as read only (Based on configuration) Load Current in Amps RMS on Line 3 - register 174 as read only (Based on configuration)

Note: Display of current on lines 1, 2, and 3 depends on the number of zones, the installed options and the load type.