![Pump Installation](/images/new-backgrounds/52280/522803x1.webp)
Operating Instructions And Parts Manual |
|
| Model ISP40 | |||
Pump Installation | 5. Connect rigid pipe to rubber boot on | If the AC/ DC Sump Pump is to be used | ||||
check valve. Tighten hose clamps. | as a backup for an electrical primary | |||||
|
| |||||
NOTICE | Installation may | Support pump and | pump it is important to maintain a | |||
take several hours. | ! WARNING piping when | minimum water level of 6 inches in the | ||||
Do not disable an existing sump pump | assembling and after installation. | sump when measured from the bottom | ||||
until you have established an | ||||||
Failure to do so could cause piping or | of the AC/ DC Sump Pump. The water | |||||
appropriate way to evacuate sump pit. | check valve to break, pump to fail, etc., | |||||
is needed to allow the AC/ DC Sump | ||||||
1. Install pump in a sump pit with | which could result in property damage | |||||
Pump to go through its | ||||||
minimum size as shown in Figure 2. | and/or personal injury. |
| ||||
6. Protect electrical cord from sharp | cycle. You will need to adjust the off | |||||
Construct sump pit of tile, concrete, | ||||||
level of the Electrical Primary Pump to | ||||||
steel or plastic. If the sump pit | objects, hot surfaces, oil and |
| ||||
| turn off at the minimum water level of | |||||
already exists, disconnect power to | chemicals. Avoid kinking the cord. | |||||
6 inches as shown in Figure 4. |
| |||||
existing pump and make certain pit | Replace a damaged cord immediately. |
| ||||
|
| |||||
is the correct size. | 7. A sump pit cover must be installed to |
|
| |||
2. The sump pump should be located | prevent debris from clogging or |
|
| |||
on a solid, level foundation. Do not | damaging the pump. |
| 22” |
| ||
place pump directly on clay, earth, | 8. Fill sump with at least 6 inches of |
| ||||
|
| |||||
gravel or a sandy surface. These | water. |
|
|
| ||
surfaces contain small stones, gravel, | Multiple pump |
|
|
| ||
sand, etc. that may clog or damage |
|
|
| |||
the pump and cause pump failure. | systems |
|
| Primary | ||
Remove any silt or debris from the |
|
| ||||
|
|
| Off Point | |||
sump pit and surrounding area. | When installing more than one pump | 6” | ||||
! WARNING | Flood risk. If | in a sump it will be necessary to decide |
| Minimum | ||
if the AC/ DC Sump Pump will be |
| Water Level | ||||
flexible discharge |
|
| ||||
hose is temporarily used, make sure | installed as a primary or as a back up | 18” Min. | Figure 4 | |||
pump is secured in sump pit to prevent | sump pump. The manufacturer | |||||
| ||||||
movement. Failure to secure pump | recommends the AC/ DC Sump Pump |
|
| |||
could result in flooding and property | be installed as a primary pump. A | The on level of the Electrical Primary | ||||
damage. |
| |||||
| conventional AC powered electrical | Pump must turn on before the 11 inch | ||||
|
| |||||
|
| back up pump can be installed | on point of the AC/ DC Sump Pump. | |||
|
| alongside as shown in Figure 3. You | Do not raise the AC/ DC Sump Pump | |||
|
| will need to raise the electrical back up | above the level of the Electrical | |||
|
| pump by placing it on a brick, or by | Primary Pump. |
| ||
|
| adjusting the float so that the |
| If it is necessary to have the primary and | ||
| 15” | electrical pump turns on above the | back up pumps discharge into a common | |||
| Min. | level of the AC/ DC Sump Pump. | line, check valves will be required on | |||
|
|
|
| both pumps to eliminate back |
| |
|
|
|
| reticulating flow into the inactive pump. | ||
|
|
|
| Battery Information | ||
|
|
|
| The system is designed to operate | ||
| 10” Dia. |
|
| most efficiently with sealed lead acid | ||
Figure 2 |
|
| (SLA) batteries at 24 volts. Two | |||
Min. |
|
| ||||
| 22” | |||||
|
|
| ||||
NOTICE | Flexible discharge |
|
| enough energy to pump more than | ||
|
| 10,000 gallons of water from a | ||||
hose is intended |
|
| ||||
|
|
|
| |||
for temporary use only. Rigid PVC or | Brick |
| basement. Deep cycle marine batteries | |||
| can also be used. |
| ||||
metal pipe is required for a permanent |
|
|
| |||
installation. |
|
|
| Sealed lead acid batteries cost slightly | ||
|
|
|
| |||
3. Thread check valve (not included) | 18” Min. | Figure 3 | more, but they can last longer. Wayne | |||
into pump body. Avoid stripping or |
|
| offers a 40 amp hour battery, 66900- | |||
cross threading. Do not use pipe |
|
|
|
| ||
joint sealant. |
| CHART 1 - STANDBY POWER PUMPING CAPACITY |
| |||
4. The pump has a |
| |||||
If the existing piping is smaller, use an | Amp Hours Per Battery | Total Gallons Pumped* |
| |||
adapter. Smaller diameter piping will |
| |||||
40.0 |
| 11,000 |
| |||
reduce the pump flow rate and |
|
| ||||
80.0 |
| 22,000 |
| |||
decrease its performance. Do not | 120.0 |
| 33,000 |
| ||
reduce below 1 1/4”. | * Assumes the sump pump is lifting water 10’ |
|
| |||
www.waynepumps.com |
|
|
|
|
Operating Instructions and Parts Manual |
| Model ISP40 |
| |||
|
|
|
|
| ||
| Troubleshooting Chart |
|
|
| ||
|
|
|
|
| ||
| Problem | Possible Cause(s) | Corrective Action |
| ||
| AC Power Indicator | 1. Power outage | 1. None |
| ||
| (red light) is not on | 2. Blown AC breaker | 2. Push AC breaker to reset. If breaker trips again, do not reset. |
| ||
|
|
|
|
| Have unit checked by qualified electrician |
|
|
| 3. GFCI tripped | 3. Reset GFCI |
| ||
|
| 4. Low AC voltage | 4. Have outlet checked by electrician |
| ||
|
|
|
|
| ||
| Alarm sounds - yellow | 1. Pump fuse may be blown | 1. Replace pump fuse. Use Bussmann AGC10 or Littlefuse 312010 |
| ||
| light is on | 2. Pump impeller may be | 2. Remove impeller. Check for damage to bore or bearing |
| ||
|
|
| damaged |
|
|
|
|
|
|
|
|
|
|
| Alarm sounds - yellow |
| Low battery |
| Apply AC power or replace batteries |
|
| light is on and red |
|
|
|
|
|
| light is off |
|
|
|
|
|
|
|
|
|
|
|
|
| Green Light is off | 1. | Battery polarity is incorrect | 1. | Recheck battery polarity |
|
|
| 2. Battery voltage too low | 2. | Replace batteries |
| |
|
|
|
|
|
|
|
| Pump will not stop | 1. | Lower float stuck | 1. | Remove filter and clean. Remove debris from float switch area |
|
|
| 2. Pump too low in sump | 2. Place a brick under the pump |
| ||
|
|
|
|
|
|
|
| Pump will not start | 1. | Pump power cord | 1. | Check for proper installation of power cord into the PS/BC |
|
|
| 2. | Upper float switch stuck | 2. | Remove filter and clean. Remove debris from float switch area |
|
|
| 3. | Impeller rotor jam | 3. | Remove filter and clean. Remove debris from float switch area |
|
|
|
|
|
|
|
|
| Pump starts/stops too | 1. | Backflow from discharge | 1. | Install or replace check valve |
|
| often |
| pipe | 2. Place a brick under the pump |
| |
|
| 2. Pump too low in sump |
| |||
|
| 3. | Clogged pump filter | 3. | Remove filter and clean |
|
|
|
|
|
|
|
|
| Pump operates but | 1. | Blocked discharge pipe | 1. | Check for restrictions in discharge line, flood is immanent. Shut |
|
| delivers little or no |
|
|
| off AC power before entering flooded area |
|
| water | 2. | Partially clogged pump | 2. | Remove impeller, check for debris in inlet |
|
|
|
| filter | 3. | Remove and inspect thrust bearing |
|
|
| 3. | Broken thrust bearing |
| ||
|
|
|
|
| ||
| “Click” inside PS/BC. | 1. Discharged battery | 1. If the battery is in otherwise good condition, it is normal for |
| ||
| An overload is |
|
|
| the circuit breaker to cycle ON and OFF several times before |
|
| indicated when you |
|
|
| the battery recovers enough to allow a normal charge rate. If |
|
| hear a distinct “click” |
|
|
| this happens on a regular basis, however, the batteries may be |
|
| from the DC circuit |
|
|
| too large for the PS/BC and it could be damaged. Replace |
|
| breaker internal to the |
|
|
| batteries |
|
| PS/BC. A | 2. Shorted cell battery | 2. A battery in this condition may cause the breaker to cycle |
| ||
| cooling off period |
|
|
| continuously. The battery will not accept a charge. Replace |
|
| occurs before the PS/BC |
|
|
| both batteries |
|
| resets itself. If the |
|
|
|
|
|
| overload condition still |
|
|
|
|
|
exists, the cycle will repeat. Regardless of what is causing the circuit breaker to cycle, unattended or routine operation in this manner could result in serious damage to the PS/BC and the battery.
www.waynepumps.com
2 | 7 |