Wayne ISP40 Pump Installation, Multiple pump, systems, Battery Information, Troubleshooting Chart

Models: ISP40

1 4
Download 4 pages 45.27 Kb
Page 2
Image 2
Pump Installation

Operating Instructions And Parts Manual

 

 

Model ISP40

Pump Installation

5. Connect rigid pipe to rubber boot on

If the AC/ DC Sump Pump is to be used

check valve. Tighten hose clamps.

as a backup for an electrical primary

 

 

NOTICE

Installation may

Support pump and

pump it is important to maintain a

take several hours.

! WARNING piping when

minimum water level of 6 inches in the

Do not disable an existing sump pump

assembling and after installation.

sump when measured from the bottom

until you have established an

Failure to do so could cause piping or

of the AC/ DC Sump Pump. The water

appropriate way to evacuate sump pit.

check valve to break, pump to fail, etc.,

is needed to allow the AC/ DC Sump

1. Install pump in a sump pit with

which could result in property damage

Pump to go through its 24-hour testing

minimum size as shown in Figure 2.

and/or personal injury.

 

6. Protect electrical cord from sharp

cycle. You will need to adjust the off

Construct sump pit of tile, concrete,

level of the Electrical Primary Pump to

steel or plastic. If the sump pit

objects, hot surfaces, oil and

 

 

turn off at the minimum water level of

already exists, disconnect power to

chemicals. Avoid kinking the cord.

6 inches as shown in Figure 4.

 

existing pump and make certain pit

Replace a damaged cord immediately.

 

 

 

is the correct size.

7. A sump pit cover must be installed to

 

 

2. The sump pump should be located

prevent debris from clogging or

 

 

on a solid, level foundation. Do not

damaging the pump.

 

22”

 

place pump directly on clay, earth,

8. Fill sump with at least 6 inches of

 

 

 

gravel or a sandy surface. These

water.

 

 

 

surfaces contain small stones, gravel,

Multiple pump

 

 

 

sand, etc. that may clog or damage

 

 

 

the pump and cause pump failure.

systems

 

 

Primary

Remove any silt or debris from the

 

 

 

 

 

Off Point

sump pit and surrounding area.

When installing more than one pump

6”

! WARNING

Flood risk. If

in a sump it will be necessary to decide

 

Minimum

if the AC/ DC Sump Pump will be

 

Water Level

flexible discharge

 

 

hose is temporarily used, make sure

installed as a primary or as a back up

18” Min.

Figure 4

pump is secured in sump pit to prevent

sump pump. The manufacturer

 

movement. Failure to secure pump

recommends the AC/ DC Sump Pump

 

 

could result in flooding and property

be installed as a primary pump. A

The on level of the Electrical Primary

damage.

 

 

conventional AC powered electrical

Pump must turn on before the 11 inch

 

 

 

 

back up pump can be installed

on point of the AC/ DC Sump Pump.

 

 

alongside as shown in Figure 3. You

Do not raise the AC/ DC Sump Pump

 

 

will need to raise the electrical back up

above the level of the Electrical

 

 

pump by placing it on a brick, or by

Primary Pump.

 

 

 

adjusting the float so that the

 

If it is necessary to have the primary and

 

15”

electrical pump turns on above the

back up pumps discharge into a common

 

Min.

level of the AC/ DC Sump Pump.

line, check valves will be required on

 

 

 

 

both pumps to eliminate back

 

 

 

 

 

reticulating flow into the inactive pump.

 

 

 

 

Battery Information

 

 

 

 

The system is designed to operate

 

10” Dia.

 

 

most efficiently with sealed lead acid

Figure 2

 

 

(SLA) batteries at 24 volts. Two 12-volt

Min.

 

 

 

22”

40-amp hour SLA batteries provide

 

 

 

NOTICE

Flexible discharge

 

 

enough energy to pump more than

 

 

10,000 gallons of water from a

hose is intended

 

 

 

 

 

 

for temporary use only. Rigid PVC or

Brick

 

basement. Deep cycle marine batteries

 

can also be used.

 

metal pipe is required for a permanent

 

 

 

installation.

 

 

 

Sealed lead acid batteries cost slightly

 

 

 

 

3. Thread check valve (not included)

18” Min.

Figure 3

more, but they can last longer. Wayne

into pump body. Avoid stripping or

 

 

offers a 40 amp hour battery, 66900-

cross threading. Do not use pipe

 

 

 

 

joint sealant.

 

CHART 1 - STANDBY POWER PUMPING CAPACITY

 

4. The pump has a 1-1/2” NPT discharge.

 

If the existing piping is smaller, use an

Amp Hours Per Battery

Total Gallons Pumped*

 

adapter. Smaller diameter piping will

 

40.0

 

11,000

 

reduce the pump flow rate and

 

 

80.0

 

22,000

 

decrease its performance. Do not

120.0

 

33,000

 

reduce below 1 1/4”.

* Assumes the sump pump is lifting water 10’

 

 

www.waynepumps.com

 

 

 

 

Operating Instructions and Parts Manual

 

Model ISP40

 

 

 

 

 

 

 

Troubleshooting Chart

 

 

 

 

 

 

 

 

 

Problem

Possible Cause(s)

Corrective Action

 

 

AC Power Indicator

1. Power outage

1. None

 

 

(red light) is not on

2. Blown AC breaker

2. Push AC breaker to reset. If breaker trips again, do not reset.

 

 

 

 

 

 

Have unit checked by qualified electrician

 

 

 

3. GFCI tripped

3. Reset GFCI

 

 

 

4. Low AC voltage

4. Have outlet checked by electrician

 

 

 

 

 

 

 

Alarm sounds - yellow

1. Pump fuse may be blown

1. Replace pump fuse. Use Bussmann AGC10 or Littlefuse 312010

 

 

light is on

2. Pump impeller may be

2. Remove impeller. Check for damage to bore or bearing

 

 

 

 

damaged

 

 

 

 

 

 

 

 

 

 

 

Alarm sounds - yellow

 

Low battery

 

Apply AC power or replace batteries

 

 

light is on and red

 

 

 

 

 

 

light is off

 

 

 

 

 

 

 

 

 

 

 

 

 

Green Light is off

1.

Battery polarity is incorrect

1.

Recheck battery polarity

 

 

 

2. Battery voltage too low

2.

Replace batteries

 

 

 

 

 

 

 

 

 

Pump will not stop

1.

Lower float stuck

1.

Remove filter and clean. Remove debris from float switch area

 

 

 

2. Pump too low in sump

2. Place a brick under the pump

 

 

 

 

 

 

 

 

 

Pump will not start

1.

Pump power cord

1.

Check for proper installation of power cord into the PS/BC

 

 

 

2.

Upper float switch stuck

2.

Remove filter and clean. Remove debris from float switch area

 

 

 

3.

Impeller rotor jam

3.

Remove filter and clean. Remove debris from float switch area

 

 

 

 

 

 

 

 

 

Pump starts/stops too

1.

Backflow from discharge

1.

Install or replace check valve

 

 

often

 

pipe

2. Place a brick under the pump

 

 

 

2. Pump too low in sump

 

 

 

3.

Clogged pump filter

3.

Remove filter and clean

 

 

 

 

 

 

 

 

 

Pump operates but

1.

Blocked discharge pipe

1.

Check for restrictions in discharge line, flood is immanent. Shut

 

 

delivers little or no

 

 

 

off AC power before entering flooded area

 

 

water

2.

Partially clogged pump

2.

Remove impeller, check for debris in inlet

 

 

 

 

filter

3.

Remove and inspect thrust bearing

 

 

 

3.

Broken thrust bearing

 

 

 

 

 

 

 

“Click” inside PS/BC.

1. Discharged battery

1. If the battery is in otherwise good condition, it is normal for

 

 

An overload is

 

 

 

the circuit breaker to cycle ON and OFF several times before

 

 

indicated when you

 

 

 

the battery recovers enough to allow a normal charge rate. If

 

 

hear a distinct “click”

 

 

 

this happens on a regular basis, however, the batteries may be

 

 

from the DC circuit

 

 

 

too large for the PS/BC and it could be damaged. Replace

 

 

breaker internal to the

 

 

 

batteries

 

 

PS/BC. A 3-5 minute

2. Shorted cell battery

2. A battery in this condition may cause the breaker to cycle

 

 

cooling off period

 

 

 

continuously. The battery will not accept a charge. Replace

 

 

occurs before the PS/BC

 

 

 

both batteries

 

 

resets itself. If the

 

 

 

 

 

 

overload condition still

 

 

 

 

 

exists, the cycle will repeat. Regardless of what is causing the circuit breaker to cycle, unattended or routine operation in this manner could result in serious damage to the PS/BC and the battery.

www.waynepumps.com

2

7

Page 2
Image 2
Wayne specifications Pump Installation, Multiple pump, systems, Battery Information, Troubleshooting Chart, Model ISP40