Majestic Appliances 36LDVR Below Grade Installations, LDVR Series Direct Vent Gas Fireplace, Step

Models: 33LDVR 43LDVR 39LDVR 36LDVR

1 40
Download 40 pages 23.84 Kb
Page 17
Image 17
Below Grade Installations

X

Always install hori- zontal venting on a level plane.

CFM136

Fig. 28 Measure horizontal length including 2” overlap.

LDVR Series Direct Vent Gas Fireplace

X

X

Manual background CFM138

Fig. 30 Horizontal length requirement.

High

Temperature Sealant

X

CFM137

Below Grade Installations

When it is not possible to meet the required vent ter- minal clearances of 12” (305mm) above grade level a snorkel vent kit #7TDVSNORK is required. It allows installation depth of down to 7” (178 mm) below grade level. The 7” is measured from the center of the hori- zontal vent pipe as it penetrates through the wall.

If venting system is installed below ground, we recommend a window well with adequate and proper drainage.

Ensure sidewall venting clearances are observed.

The maximum horizontal run with 24” vertical rise is 36” (914 mm) from the back of the fireplace to the face of the exterior wall. See vent graph (Page 12) for extended horizontal run if the vertical rise exceeds 24” (610 mm).

Fig. 29 Apply high temperature sealant.

STEP 6

Apply high temperature sealant to 4” (102 mm) and 7” (178 mm) collars or the termination one inch away from the end. Guide the vent terminationʼs 4” and 7” collars into their respective vent pipes. Double check that the vent pipes overlap the collars by 2” (50 mm). Secure the termination to the wall with screws provided and caulk around the wall plate to weatherproof. (Fig. 30)

STEP 7

Support the horizontal pipes every 36” (914 mm) with metal pipe straps. Make sure that the horizontal vent pipe is installed on a level horizontal plane.

STEP 8

Re-check the fireplace to make sure that it is levelled, properly positioned, and nailed or screwed to the floor. If applied, the fireplaces adjustable frame drywall strips (nailing flanges) should be fastened. Refer to “Framing & Finishing”.

1.Establish vent hole through the wall. (Fig. 25)

2.Remove soil to a depth of approximately 16” (406mm) below base of snorkel. Install window well (not supplied). Refill hole with 12” (305 mm) of coarse gravel leaving a clearance of approximately 4” (102 mm) below snorkel. (Fig. 31)

3.Install vent system. See Page 13, Steps 2 through 5.

4.Ensure a watertight seal is made around the vent pipe coming through the wall.

5.Apply high temperature sealant caulking (supplied) around the 4” and 7” snorkel collars.

6.Slide into the vent pipe and secure to the wall.

7.Level the soil to maintain a 4” (102 mm) clearance below snorkel. (Fig. 31)

10007317

17

Page 17
Image 17
Majestic Appliances 36LDVR, 33LDVR, 39LDVR Below Grade Installations, LDVR Series Direct Vent Gas Fireplace, Step, 10007317