Majestic Appliances 33LDVR Vertical Sidewall Installation, LDVR Series Direct Vent Gas Fireplace

Models: 33LDVR 43LDVR 39LDVR 36LDVR

1 40
Download 40 pages 23.84 Kb
Page 16
Image 16
Vertical Sidewall Installation

LDVR Series Direct Vent Gas Fireplace

Vertical Sidewall Installation

STEP 1

Locate vent opening on the wall. It may be necessary to first position the fireplace and measure to obtain hole location. Depending on whether the wall is combustible or noncombustible, cut opening to size. (Fig. 25)

For combustible walls first frame in opening.

Combustible Walls (Fig. 25): Cut a 9³⁄”H x 9³⁄” W (240 x 240mm) hole through the exterior wall and frame.

Noncombustible Walls (Fig. 25): Hole opening must be 7.5” (190mm) in diameter.

Vent Opening for Combustible Wall

9³⁄

(240mm)

9³⁄

(240mm)

Framing Detail

Fireplace Hearth

Opening for Noncombustible Wall

7¹⁄

(190mm)

VO584-100

Fig. 25 Locate vent opening on wall.

STEP 2

Measure wall thickness and cut adjustable zero clearance sleeve parts to proper length (MAXIMUM 12”/305mm). (Fig. 26) Adjust sleeve to minimum (9³⁄” x 9³⁄” and attach to firestop with #8 sheet metal screws (supplied). Assemble sleeve and attach to firestop with #8 sheet metal screws (supplied). Install firestop as- sembly.

Zero clearance sleeve is only required for combustible walls.

STEP 3

Apply a bead of high temperature sealant to the inner and outer flue collars of the fireplace and using ap- propriate venting component(s) attach to fireplace with three (3) screws. (Fig. 27) Follow with the installation of the inner and outer elbow. Again secure joints with three (3) sheet metal screws. Wipe off any excess high temperature sealant.

Adjustable Zero Clear-

Maximum Length

ance Sleeve

 

 

 

12” (305mm)

 

 

#8 Screws (2)

#8 Screws

 

 

(2)

 

Adjust-

 

 

able Zero

 

#8 Screws (2)

Clearance

Wall Exterior

Sleeve

Wood Framing

 

Firestop

Firestop

Zero Clearance

Sleeve Flush with

 

Wall Exterior

Vent Pipe

 

 

Drywall

 

CFM135

 

 

Fig. 26 Locate vent opening on wall.

Ensure Pipes are

Concentric

��������

Bead of Seal- ant

(If necessary)

CFM143

Fig. 27 Apply sealant to inner and outer pipe.

STEP 4

Measure the horizontal length requirement including a 2” (50mm) overlap, i.e. from the elbow to the outside wall finish plus 2”, or the distance required if installing a second 90° elbow. (Fig. 28)

STEP 5

Use appropriate length of pipe section - telescopic or fixed - and install the horizontal vent sections. The 20” (508mm) section of pipe which goes through the wall is packaged with the 7TDVSK starter kit, and can be cut to suit if necessary. (Fig. 29)

Sealing vent pipe and firestop gaps with high temperature sealant will restrict cold air being drawn in around fireplace.

16