PLUS Line Instruction Manual Supplement
PLUS & PLUS WATER HEATERS WITH
2 Install boiler-to-water heater piping
Combined space heating/water heating applications
1.Figure 4 shows recommended piping between Ultra Boiler and PLUS water heater. All show direct connection of the water heater piping to the boiler because the boiler circulator shuts down during water heater operation.
2.Table 1, page 7, uses the recommended flow rates for the Ultra PLUS water heater and minimum flow rates for the Ultra boiler to provide recommended water heater piping and circulator sizing. If using another circulator, verify it is at least equal to the Taco selection given in Table 1. For general information on head loss through boiler and boiler-
3.Procedure:
Step 1: Select Ultra Boiler model and PLUS water heater model in Table 1.
Step 2: Read recommended minimum flow rate, GPM, in table.
Step 3: Read across to find recommended minimum pipe size for
Step 4: Read across to find recommended Taco circulator model. Use a circulator with a pump curve at least equal to the Taco circulator shown. See Figure 6, page 7 for pump curves of typical Taco circulators.
Dedicated water-heating only applications
1.Figure 5 shows recommended piping between Ultra Plus Boiler and PLUS water heater for dedicated
2.Pipe sizing:
Table 2, page 7, provides the recommended minimum pipe size for
3.Circulator:
Use the circulator recommended in Table 2, page 7. Install the circulator as shown in Figure 5.
4.Procedure:
Step 1: Select Ultra Boiler model and PLUS water
heater model in Table 1, page 7.
Step 2: Read flow rate expected using the circulator specified inthe last column.
Step 3: Size connecting piping as listed under “Boiler piping” in the table.
Figure 4 | Figure 5 |
Combined space heating/water | Dedicated |
heating application | application |
3Boiler relief valve (see Boiler Manual for piping details)
4Relief valve discharge piping (see Boiler Manual for details)
5Water heater circulator — must be at least equal in capacity to circulator recommended in Table 1, page 7
6Isolation valves
10Flow/check valve (with weighted seat to prevent gravity circulation)
11Purge/drain valves
3Boiler relief valve (see Boiler Manual for piping details)
4Relief valve discharge piping (see Boiler Manual for details)
5Water heater circulator — (see Table 2, page 7)
8Expansion tank (diaphragm or bladder type)
6Isolation valves
10Flow/check valve (with weighted seat)
11Purge/drain valve
20 Fill line to fill valve (item 23)