Weil-McLain Electric Water Heater Zoning with circulators, Circulator zoning plus optional

Models: Electric Water Heater

1 12
Download 12 pages 52.29 Kb
Page 5
Image 5
Zoning with circulators

PLUS Line Instruction Manual Supplement

PLUS & Figure 3 Circulator zoning plus optionalManual backgroundManual background PLUS WATER HEATERS WITH Manual backgroundManual backgroundManual background GAS-FIRED WATER BOILERS

1 Install system water piping (space heating) (continued)

Zoning with circulators

Figure 3 Circulator zoning plus optional

1.

Connect boiler to system as shown in Figure 3

water heater piping

 

 

when circulator zoning. The boiler circulator

 

 

cannot be used for a zone. It must supply only the

 

 

boiler loop.

 

 

2.

Install a separate circulator for each zone.

 

3.

When using a closed-type expansion tank, connect

 

 

the expansion tank and make-up water piping as

 

 

shown in Figure 1, page 3.

 

4.

Connect water heater (domestic hot water) piping

 

 

to indirect storage water heater as shown.

 

 

 

The

PhDControl Module turns off

 

 

 

 

space heating during water heater heating. The boiler circulator will turn off, preventing hot water from circulating to the system. The flow/check valve shown on the boiler outlet piping prevents gravity circulation in the boiler loop during water heater heating.

NOTE 1: To ensure adequate flow rate through the boiler, use the following pipe size on all boiler loop piping (connecting boiler to and from the primary/secondary connection, item 21):

Ultra-80 or Ultra-105 – 1" or larger. Ultra-155 or Ultra-230 – 1¼" or larger. Ultra-310 – 1½" or larger.

Use at least the minimum piping size above and pipe the boiler using only primary/ secondary piping as shown. Failure to follow these guidelines could result in system problems.

Legend

Figure 3

1Ultra boiler

2Indirect water heater (water heater), if used

3Boiler relief valve (see boiler manual for piping details)

4Relief valve discharge piping (see boiler manual for details)

5Water heater circulator (see page 7 for suggested sizing)

6Isolation valves

7System circulator

8Diaphragm (or bladder) type expansion tank (see page 3 for piping of closed-type expansion tank, if used)

9Air separator [with automatic air vent only on systems using diaphragm (or bladder) type expansion tank]

10Flow/check valves (with weighted seats to prevent gravity circulation)

11Purge/drain valves

12Boiler circulator

14 Zone circulators, typical

20Make-up water supply

21Primary/secondary connection

Part number IWHA016A/1103

5

Page 5
Image 5
Weil-McLain Electric Water Heater Zoning with circulators, Install system water piping space heating continued