Weil-McLain Electric Water Heater Install boiler-to-water heater piping continued, Tables 1 and

Models: Electric Water Heater

1 12
Download 12 pages 52.29 Kb
Page 7
Image 7
2 Install boiler-to-water heater piping (continued)

PLUS Line Instruction Manual Supplement

PLUS & Table 1 Combined space heating/water heating applications (see Notes)Tables 1 and 2Figure 6 Pump curves for Taco circulators PLUS WATER HEATERS WITH Manual backgroundManual backgroundManual background GAS-FIRED WATER BOILERS

2 Install boiler-to-water heater piping (continued)

Table 1 Combined space heating/water heating applications (see Notes)

Table 2 Dedicated water-heating only systems (using circulator supplied with boiler) (see Notes)

Notes

Tables 1 and 2

Figure 6 Pump curves for Taco circulators

1.First hour ratings in Tables 1 and 2 are based on:

115°F or 140°F domestic outlet water supply temperature from water heater.

50°F domestic water inlet temperature.

190°F boiler water temperature leaving Ultra boiler.

Circulator and pipe sizes as given in the Tables.

2.If the net Btu/hr rating of the boiler is close to the space heating load (for combined systems) — or if there is an unusually large demand for domestic water — increased boiler capacity may be required.

Part number IWHA016A/1103

7

Page 7
Image 7
Weil-McLain Electric Water Heater Install boiler-to-water heater piping continued, PLUS Line Instruction Manual Supplement