PLUS Line Instruction Manual Supplement
PLUS & PLUS WATER HEATERS WITH
1 Install system water piping (space heating) (continued)
Zoning with zone valves | Figure 2 Zone valve zoning plus optional | |||
1. | Connect boiler to system as shown in Figure 2 | water heater piping | ||
| ||||
| when zone valve zoning. The primary/secondary |
| ||
| piping shown ensures the boiler loop will have |
| ||
| sufficient flow. It also avoids applying the high head |
| ||
| of the boiler circulator to the zone valves. |
| ||
2. | When using a |
| ||
| the expansion tank and |
| ||
| shown in Figure 1, page 3. |
| ||
3. | Connect water heater (domestic hot water) piping |
| ||
| to indirect storage water heater as shown. |
| ||
|
| The | PhDControl Module turns off |
|
|
|
|
space heating during water heater heating. The boiler circulator will turn off, preventing hot water from circulating to the system. The flow/check valve shown on the boiler outlet piping prevents gravity circulation in the boiler loop during water heater heating.
4.Controlling the system circulator
a.To cycle the system circulator from the Ultra PhD control module, add a circulator relay wired to the boiler circulator terminals as shown on page 8.
NOTE 1: To ensure adequate flow rate through the boiler, use the following pipe size on all boiler loop piping (connecting boiler to and from the primary/secondary connection, item 21):
Use at least the minimum piping size above and pipe the boiler using only primary/ secondary piping as shown. Failure to follow these guidelines could result in system problems.
Legend | Figure 2 |
1Ultra boiler
2Indirect water heater (water heater), if used
3Boiler relief valve (see boiler manual for piping details)
4Relief valve discharge piping (see boiler manual for details)
5Water heater circulator (see page 7 for suggested sizing)
6Isolation valves
7System circulator
8Diaphragm (or bladder) type expansion tank (see page 3 for piping of
9Air separator [with automatic air vent only on systems using diaphragm (or bladder) type expansion tank]
10Flow/check valves (with weighted seats to prevent gravity circulation)
11Purge/drain valves
12Boiler circulator
13Zone valves, typical
20
21Primary/secondary connection
4 | Part number IWHA016A/1103 |