Electrical requirements
Observe all governing Codes and Ordinances.
1.A two wire, single phase, 220 Volt, 50 Hz, AC only. electrlcal power supply ISrequired on a separately fused 15 Ampere circuit (Time delay fuse or circuit breaker is recommended )
2.An adequate electrical ground is required within 4 feet of the appliance location when using the grounding wire supplied
3.THE DRYER MUST BECONNECTED TO COPPER WIRE ONLY. Aluminum wire must not be used to avoid
potentially unsatisfactory connections.
4.Local codes may permit the use of a flexible type electrical power supply cord [pigtail), A suitable strain relief must be provided at the point the power supply cord enters the appliance
5.The appliance may be connected directly to the fused dtsconnect [or circuit breaker) box through flexible armored or
[I5 Amperes). DO NOT use an extension cord.
Electrical
Connection
220 Volt - Single Phase -
Electrical ground is required on this appliance.
This cppliance is manufactured with the neutral terminal NOT connected to the frame.
CONNECT GROUND
TO FUSED | DIS- | II | 64 |
|
| |
SUPPLY | CORD |
|
|
|
|
|
| \ |
| )+p\ |
|
|
|
Figure | 1 |
|
| POWER | SUPPLY | CORD |
|
|
|
| (WITH | STRAIN | RELIEF) |
|
|
| / | (15 AMPERES) |
| |
Connect | the power | supply | cord | |||
as follows: |
|
|
|
|
|
1.Remove the terminal block cover
2.Connect the two wires of the power supply cord to the outer terminals of the terminal block. See Figure 1. For connecting
3.Replace terminal block cover,
NOTE
the power supply cord to electric power supply until appliance is permanently grounded.
Exhaust requirements
WARNING:
l Metal flexible duct may be used
For Safety:
lDo not exhaust dryer Into a chimney, furnace cold air duct, atiic or crawl space, or any other duct used for venting Accumulated lint could become a fire hazard or moisture could cause damage,
l Clean the exhaust system perlodically, at least every 2 years
l Never install flexible duct concealed In walls, ceiling or under flooring.
Four Inch Metal Exhaust Duct is recommended.
(Do not use
Exhausting the dryer outside is recommended If you cannot exhaust the dryer to the outside, use Exhaust Deflector Kit LCK4000 available from vour WhirlDo01 dealer
of the dryer back.
The Exhaust Duct can be routed up, down, left, right or straight out the back of the dryer
Metal Flexible Duct must be fully extended and supported when the dryer ISin its final position, DO NOT KINK OR CRUSH THE DUCT
An Exhaust Hood should cap
exhaust duct to prevent exhausted air returning into dryer, The outlet of the hood must be at least 12 Inches from the ground or anything else that may be
in the path of the exhaust,
A 2% inch outlet Exhaust Hood should be used with short systems only, [This outlet creates greater back pressure than other hood types.)
Exhaust Hoods with magnetic latches should not be used.
The Maximum Length of the exhaust system depends upon the type of duct used, number of elbows and type of exhaust hood The maximum length for both rigid and flexible duct is shown In chart
l Accumulate lint.
For Exhaust Systems not covered by the exhaust length chart, see WhIrlpool Service Manual, Exhausting Whirlpool Dryers, Part No 603197 available from your Whirlpool parts distributor. The back pressure in any exhaust system used must not exceed .6 inches 0f water column measured with an inclined manometer at the point that the exhaust system connects to the dryer
There are Exhaust Kits available that allow you to direct filtered exhaust air Inside to conserve energy during winter months. Whirlpool has a
or local codes, If you use one of these kits, be aware that excessive moisture in the home can cause many problems and that you may see an increase in the time required to dry a load. Also, you must regularly clean the filter to avoid excessive lint
NOTE: Do not use this kit on a dryer installed in a bedroom, bathroom, or closet.
Recessed Area
Instluctions
INSTRUCTIONS FOR RECESSED OR CLOSET INSTALLATIONS
The following installation spacings and door air openings for the dryer are possible when installed and exhausted as noted. [Spacing as indicated is in inches and is minimum allowable. For ease of installation and service, additional spacing should be considered.)
TO PREVENT LARGE AMOUNTS OF LINT AND MOISTURE FROM ACCUMULATING AND TO MAINTAIN DRYING EFFICIENCY, THIS MACHINE MUST BE EXHAUSTED OUTDOORS.
MINIMUM INSTALLATION SPACING
~
CONNECT GROUND
WIRE TO APPROVED
GROUND
v
NUMBER
I
EXHAUST HOOD TYPE
1
Unobstrucled air openings requtred for laundry equ,pmenr when door IS installed
pk
| POWER | SUPPLY | CORD |
Figure 2 | (WITH | STRAIN | RELIEF) , |
(15 AMPERES) |
|
4.Connect a separate copper grounding wire (No 10 minimum] to a grounded cold water pipe” my means of a clamp and then to the frame of the appliance at the external grounding connector. Use Part No. 685463 grounding wire and clomp assembly. Do not ground to a gas supply pipe Do not connect
PANEL B
1 | 0 | 43 | FT | 41 | FT. | 36 | Fl | 1 LENGTHMAXIMUM |
| |
| 1 | 33 | FT | 31 | FT. | 26 | FT | OF 4’ DIA |
| |
| 2 | 23 | FT | 21 | FT | 16 | FT. | DUCTRIGID | METAL | ~ |
|
|
|
|
|
|
|
|
|
| I |
|
|
|
|
|
|
|
| MAXIMUM | ~ | |
| 0 | 30 | FT | 29 | FT | 24 | FT | LENGTH | OF |
|
| 1 | 24 | FT | 23 | FT | 1.9 FT | 4” DIA |
| I | |
|
|
|
|
|
|
|
| FLEXIBLE |
| |
| 2 | 16 | FT | 15 | FT | 10 | FT | METAL | DUCT, |
|
Exhaust Systems longer than specified will:
lShorten the life of the dryer
l Reduce the performance in ways such as causing longer drying times and increasing the use of energy.
_=Louvered door with eaulva.ert air ooenlngs ISacceptable
’__“D” Dlmenslon must be measure5 from dryer cabinet rear panel
Companion appliance spacings should be considered.
Detailed space requirements can be found on the label located on the back panel of dryer.
NOTE, No other fuel burning appliance may be installed in the same closet