Installation instructions
How to Purge Air Tubes:
(1). Unscrew and remove caps from 2 and
(2). Unscrew and remove cap from service valve.
(3). Connect vacuum pump flexible hose to the service valve.
(4). Start vacuum pump for
(5). With vacuum pump still running close the low pressure knob on vacuum pump manifold. Then stop vacuum pump.
(6). Open
(7). Turn 2 and
(8). Replace and tighten all valve caps.
Notes
Please read this manual before installing and using it.
Do not let air enter the refrigeration system or discharge refrigerant when moving the air conditioner.
Testing run the air conditioner after finishing installation, and record details of operation.
Type of fuse used on indoor unit controller is 50T, with rating 2.5A,AC250V.
The fuse for the whole unit is to be provided by the user according to the current at maximum power
Input or use other
Only the air conditioner can be connected to the power line.
The power connection for the air conditioner has to be done at the main power distribution which has to be of a low impedance.
In order to ensure the suitability of the equipment for connection, the user should consult with the supply authority, if necessary, that the service current capacity at the interface point is sufficient for the equipment.
Refer to the rating plate of the equipment for power consumption details.
If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or similarly qualified person in order to avoid a hazard.