Models: 192906 BFG1F4034T3PV BFG1F4034T3PV 7K 195102 211456 BFG1F3030S3NOV BFG1H4040T3NOV 5K BFG2H5040T3NOV 7K 188424 211458 BFG2J5040T3NOV 7K 211454 221208 198984 BFG1J4040T3NOV 5K 195863 211304 BFG1F4034T3NOV 5K BFG1F5040T3PV BFG1H4040S3NOV 211360 4220 BFG1F5040T3PV 7K 192868 211289 BFG1F4040T3NOV 5K BFG1F5050T4NOV 145232 BFG2H4040T3NOV 7K BFG2H4040T3NOV E BFG2F4040S3PV ES 211450 SG1J5040T3NOV STP WP 5K SG1J5040T3NOV 5K 211462 BFG2H5040T3NOV E BFG1H5040T3NOV 5K 199748 211364 211446 BFG1F4040T3NOV BFG1F5040T3NOV STP WP5K LDO'06 216071 BFG1F4040T3NOV 7K BFG1F5040T3NOV 5K BFG1J4040T3NOV 7K 12307 187122 BFG1F4040T3NOV STP WP7K LDO'06 BFG1F3030T3NHV BFG2J5040T3NOV E 195207 211377 BFG1F4040T3NOV STP WP5K LDO'06 BFG1F3030T3PV BFG1F3030S3PV BFG2F4040T3NOV 7K BFG1F5040T3NOV 7K BFG2F4040T3NOV E

1 28
Download 28 pages 29.38 Kb
Page 10
Image 10
Vent Pipe System

Vent Pipe System

This water heater uses a non-direct, single-pipe vent system to remove exhaust gases created by the burning of fossil fuels. Air for combustion is taken from the immediate water heater location or is ducted in from the outside (see “Combustion Air Supply and Ventilation”).

This water heater must be properly vented for the removal of exhaust gases to the outside atmosphere. Correct installation of the vent pipe system is mandatory for the proper and efficient operation of this water heater and is an important factor in the life of the unit.

The vent pipe must be installed according to all local and state codes or, in the absence of local and state codes, the “National Fuel Gas Code”, ANSI Z223.1(NFPA 54)-latest edition. The vent pipe installation must not be obstructed so as to prevent the removal of exhaust gases to the outside atmosphere.

IMPORTANT: The use of vent dampers is not recommended by the manufacturer of this water heater. Although some vent dampers are certified by CSA International, this certification applies to the vent damper device only and does not mean they are certified for use on this water heater.

U.L. recognized fuel gas and carbon monoxide (CO) detectors are recommended in all applications and should be installed using the manufacturer’s instructions and local codes, rules, or regulations.

IMPORTANT: If you lack the necessary skills required to properly install this venting system, you should not proceed, but get help from a qualified person.

Drafthood Installation

Align the legs of the drafthood with the slots provided. Insert the legs and secure the drafthood to the water heater’s top with the four screws provided as shown in Figure 9. Do not alter the drafthood in any way. If you are replacing an existing water heater, be sure to use the new drafthood supplied with the water heater.

Figure 9

Drafthood Installation

Sheet Metal Screws (four provided)

 

Legs

 

 

 

 

 

 

Drafthood

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Legs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Slots

 

 

 

 

 

 

 

 

 

Slots

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Jacket top

 

 

 

 

 

 

 

 

Install the drafthood with

 

 

 

the four screws provided.

Vent Pipe Size

It is important that you follow the guidelines in these instructions for sizing a vent pipe system. If a transition to a larger vent size is required, the vent transition connection must be made at the drafthood outlet.

Vent Connectors

1.Type B, Double wall, U.L. Listed Vent Pipe.

2.Single wall Vent Pipe.

Maintain the manufacturer’s specified minimum clearance from combustible materials when using type B double wall vent pipe.

Vent connectors made of type B, double wall vent pipe material may pass through walls or partitions constructed of combustible material if the minimum listed clearance is maintained.

Maintain a six inch minimum clearance from all combustible materials when using single wall vent pipe.

IMPORTANT: Single wall vent pipe cannot be used for water heaters located in attics and may not pass through attic spaces, crawl spaces or any confined or inaccessible location. A single wall metal vent connector cannot pass through any interior wall.

When installing a vent connector, please note the following:

Install the vent connector avoiding unnecessary bends, which create resistance to the flow of vent gases.

Install without dips or sags with an upward slope of at least 1/4-inch per foot.

Joints must be fastened by sheet metal screws or other approved means. It must be supported to maintain clearances and prevent separation of joints and damage.

The length of the vent connector cannot exceed 75% of the vertical vent height.

The vent connector must be accessible for cleaning, inspection, and replacement.

Vent connectors cannot pass through any ceiling, floor, firewall, or fire partition.

IMPORTANT: Existing vent systems must be inspected for obstructions, corrosion, and proper installation.